Plan Review Notes For Permit 03120934 |
Permit Number |
03120934 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-31 00:00:00 | ************* UNSAT ************** | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH PANEL SCHEDULE. | | SOME SHOWN AS XX. | | | | 2)NOTE: PLEASE CLARIFY NEW/ EXISTING | | REQ'D SIGN CIRCUIT PER 600.5 | | APPEARS TO BE SHOWN ON PANEL SCHEDULE, | | PLEASE SHOW ON PLANS. | | | | 3)NOTE: PLEASE SHOW/LABEL AND MAP AREA | | FOR SPRAY BOOTH PER NEC 516 AND LABEL | | AREAS ON PLANS FOR NEC 511. | | PLEASE CLARIFY IF LIGHTING ETC WILL BE | | PART OF BOOTH? PLEASE ALSO PROVIDE | | APPLICABLE MANF. SPECS FOR BOOTH. | | | | 4)NOTE: PLEASE INLCUDE ADDRESS OF JOB | | ON TITLE BLOCK AS REQ'D UNDER FS | | FAC 61G1-16.004, 61G15-23.002. | | | | 5)NOTE: PLEASE INCLUDE FOOTER STEEL AS | | PART OF THER GROUNDING ELECTRODE SYSTEM | | PER 250.50 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | PLEASE SEE FIRE REVIEW COMMENTS AS THEY | | WILL HAVE A DIRECT AFFECT ON ELECTRICAL | | PLANS. |
|