 BUILDING PLAN REVIEW
 PERMIT: 03120934
 ADD: 2275 PALM BEACH LAKES BLVD
 CONT: HALLMARK
 TEL: (561)512-5517
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE TYPES OF FLAMMIBLE AND COMBUST-
 IBLE MATERIALS TO BE STORED AND THE
 AMOUNTS TO BE STORED, THIS WILL DETER-
 MINE WHAT TYPE OF OCCUPANCY THE SPRAY
 BOOTH AND SURROUNDING WORK AREA WILL BE
 CLASSIFIED AS. FOR THIS REVIEW THE CLASS
 IFICATION WILL BE HAZARDOUS; H2, DEFLAG-
 RATION HAZARDS INCLUDE CLASS I,II AND
 III-A FLAMMABLE LIQUIDS IN OPEN CONTAIN-
 ERS OR CONTAINERSPRESSURED AT MORE THAN
 15 PSI.
 PROVIDE INFORMATION FROM TABLE 308.2B
 FOR "EXEMPTION" EXEMPT QUANITIES OF H2
 MATERIALS.
  
 2) SPRAY BOOTH: 407.1.3.5 SPRAY BOOTHS
 WHERE FLAMMABLE MATERIALS ARETO BE USED
 SHALL BE PROTEDCTED BY AN AUTOMATIC
 SPRINKLER SYSTEM.
  
 3) PLANS DO NOT INDICATE FIRE SPRINKLERS
 FOR A TYPE V BUILDING, H2 OCCUPANCY,
 TABLE 500 REQUIRES EITHER 1HR PROTECTED
 FOR 7,500 SQ FT OR UNPROTECTED, SPRINK-
 LERED FOR 4,000 SQ FT. WITH THE ADDITION
 GROSS AREA IS 7003.15= 55'X127'-4".
 ONCE AMOUNTS OF FLAMMIBLE LIQUIDS ARE
 CONFIRMED AND THE AMOUNTS ARE ALLOWABLE
 BY TABLE 308.2B THE H2 OCCUPANCY WILL
 BE DOWN GRADED TO STORAGE, TYPE V BUILD-
 ING, UNPROTECTED.SPECIAL STORAGE OCC.
 411.5.1.
  
 4) OCCUPANCY SEPERATION, SEPERATION
 FROM THE WORK AREA TO BUSINESS OCCUPANCY
 REQUIRES A (2HR WALL) 1 1/2 HR OPENING
 PROTECTIVES).
  
 5) THIS BUILDING IS LOCATED IN A FIRE
 DISTRICT, F102.2.7 ARCHITECTURAL TRIM ON
 BUILDINGS LOCATED IN A FIRE DISTRICT
 SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD. PROVIDED FIRE RESISTANCE RATING
 BASED ON TESTS CONDUCTED IN ACCORDANCE
 WITH ASTM 119.
 THE ARCH AND STRUCTURAL PAGES BOTH
 INDICATE USE CDX PLYWOOD ON THE FRONT
 AND BACK OF THE TOWER & WALL EXTENSIONS,
 THIS CONSTITUTES TYPE VI CONSTRUCTION,
 NOT ALLOWED IN THE "FIRE DISTRICT".
 F102.1. THIS ALSO INCLUDES GIRDER TRUSS-
 ES MAKING UP WALL PANELS OF TOWER.
  
 6)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE MULTIPLE PAGES, (2) A2,
 (3) A4,PLEASAE PULL OLD SHEETS, OR IF
 ALL SHEETS ARE APPLICABLE RENUMBER, ALSO
 DESIGNATE WHICH DETAILS BELONG TO WHICH
 BUILDING.
 DOOR & WINDOW OPENINGS BELONGING TO
 SOUND ADVISE AND ARE "NEW" DO NOT SHOW
 UP ON THE DOOR WINDOW SCHEDULE.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED SING DOORS
 B) GLAZED SWING DOORS W/ SIDELIGHTS
 C) GLAZED SWING DOORS W/ SIDELIGHTS &
 TRANSOM
 D) MULLIONS, VERTICAL & HORIZONTAL
 E) WINDOWS
 F) STORM SHUTTERS IF IMPACT GLAZING
 NOT USED
 G) LOUVERS
 H) PANEL WALLS, INCLUDING EFIS, FOAM
 MOLDINGS
 I) ROOFING ASSEMBLIES
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 12)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 13)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
  
 14) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 15) FL BLD CODE 104.2.1.2
 0DDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, SHEET A-4 CARSMETIC ELE.
 VS. S3 SPECIFICATION AS A COSTAL ZONE,
 HIGHER NEGITIVE PRESSURES, INDICATE
 THESE INCREASED PRESSURES FOR ALL OPEN-
 INGS, INDICATE FOR ALL ELEVATIONS,
 BOTH BUILDINGS.
  
 16) S3 INDICATES ENGINEERING CRITERIA,
 TRUSSES NO BOTTOM CHORD LIVE LOAD,
 10 LBS. (TABLE 1604.1)
  
 17) TRUSS ANCHOR SCHEDULE, RE-EVALUATE
 TO FLORIDA SPECIFIC, SEE VALUES IN
 USP CATOLOG IN GRAY SHADING NO ADDITION-
 AL STRESS ON STEEL CALCULATIONS.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 18)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 19)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.