2004-01-15 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 03120934 |
| ADD: 2275 PALM BEACH LAKES BLVD |
| CONT: HALLMARK |
| TEL: (561)512-5517 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PROVIDE TYPES OF FLAMMIBLE AND COMBUST- |
| IBLE MATERIALS TO BE STORED AND THE |
| AMOUNTS TO BE STORED, THIS WILL DETER- |
| MINE WHAT TYPE OF OCCUPANCY THE SPRAY |
| BOOTH AND SURROUNDING WORK AREA WILL BE |
| CLASSIFIED AS. FOR THIS REVIEW THE CLASS |
| IFICATION WILL BE HAZARDOUS; H2, DEFLAG- |
| RATION HAZARDS INCLUDE CLASS I,II AND |
| III-A FLAMMABLE LIQUIDS IN OPEN CONTAIN- |
| ERS OR CONTAINERSPRESSURED AT MORE THAN |
| 15 PSI. |
| PROVIDE INFORMATION FROM TABLE 308.2B |
| FOR "EXEMPTION" EXEMPT QUANITIES OF H2 |
| MATERIALS. |
| |
| 2) SPRAY BOOTH: 407.1.3.5 SPRAY BOOTHS |
| WHERE FLAMMABLE MATERIALS ARETO BE USED |
| SHALL BE PROTEDCTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM. |
| |
| 3) PLANS DO NOT INDICATE FIRE SPRINKLERS |
| FOR A TYPE V BUILDING, H2 OCCUPANCY, |
| TABLE 500 REQUIRES EITHER 1HR PROTECTED |
| FOR 7,500 SQ FT OR UNPROTECTED, SPRINK- |
| LERED FOR 4,000 SQ FT. WITH THE ADDITION |
| GROSS AREA IS 7003.15= 55'X127'-4". |
| ONCE AMOUNTS OF FLAMMIBLE LIQUIDS ARE |
| CONFIRMED AND THE AMOUNTS ARE ALLOWABLE |
| BY TABLE 308.2B THE H2 OCCUPANCY WILL |
| BE DOWN GRADED TO STORAGE, TYPE V BUILD- |
| ING, UNPROTECTED.SPECIAL STORAGE OCC. |
| 411.5.1. |
| |
| 4) OCCUPANCY SEPERATION, SEPERATION |
| FROM THE WORK AREA TO BUSINESS OCCUPANCY |
| REQUIRES A (2HR WALL) 1 1/2 HR OPENING |
| PROTECTIVES). |
| |
| 5) THIS BUILDING IS LOCATED IN A FIRE |
| DISTRICT, F102.2.7 ARCHITECTURAL TRIM ON |
| BUILDINGS LOCATED IN A FIRE DISTRICT |
| SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE |
| MATERIALS OR FIRE RETARDANT TREATED |
| WOOD. PROVIDED FIRE RESISTANCE RATING |
| BASED ON TESTS CONDUCTED IN ACCORDANCE |
| WITH ASTM 119. |
| THE ARCH AND STRUCTURAL PAGES BOTH |
| INDICATE USE CDX PLYWOOD ON THE FRONT |
| AND BACK OF THE TOWER & WALL EXTENSIONS, |
| THIS CONSTITUTES TYPE VI CONSTRUCTION, |
| NOT ALLOWED IN THE "FIRE DISTRICT". |
| F102.1. THIS ALSO INCLUDES GIRDER TRUSS- |
| ES MAKING UP WALL PANELS OF TOWER. |
| |
| 6)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PLANS INDICATE MULTIPLE PAGES, (2) A2, |
| (3) A4,PLEASAE PULL OLD SHEETS, OR IF |
| ALL SHEETS ARE APPLICABLE RENUMBER, ALSO |
| DESIGNATE WHICH DETAILS BELONG TO WHICH |
| BUILDING. |
| DOOR & WINDOW OPENINGS BELONGING TO |
| SOUND ADVISE AND ARE "NEW" DO NOT SHOW |
| UP ON THE DOOR WINDOW SCHEDULE. |
| |
| 7) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) GLAZED SING DOORS |
| B) GLAZED SWING DOORS W/ SIDELIGHTS |
| C) GLAZED SWING DOORS W/ SIDELIGHTS & |
| TRANSOM |
| D) MULLIONS, VERTICAL & HORIZONTAL |
| E) WINDOWS |
| F) STORM SHUTTERS IF IMPACT GLAZING |
| NOT USED |
| G) LOUVERS |
| H) PANEL WALLS, INCLUDING EFIS, FOAM |
| MOLDINGS |
| I) ROOFING ASSEMBLIES |
| |
| 8)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 9)1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 11)PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| |
| 12)FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 13)1707.4.4.2 TAPERED BUCKS: |
| SHALL EXTEND BEYOND THE INTERIOR FACE |
| OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| |
| |
| 14) 1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. |
| |
| 15) FL BLD CODE 104.2.1.2 |
| 0DDITIONAL INFORMATION REQUIRED, |
| DISCREPANCY, SHEET A-4 CARSMETIC ELE. |
| VS. S3 SPECIFICATION AS A COSTAL ZONE, |
| HIGHER NEGITIVE PRESSURES, INDICATE |
| THESE INCREASED PRESSURES FOR ALL OPEN- |
| INGS, INDICATE FOR ALL ELEVATIONS, |
| BOTH BUILDINGS. |
| |
| 16) S3 INDICATES ENGINEERING CRITERIA, |
| TRUSSES NO BOTTOM CHORD LIVE LOAD, |
| 10 LBS. (TABLE 1604.1) |
| |
| 17) TRUSS ANCHOR SCHEDULE, RE-EVALUATE |
| TO FLORIDA SPECIFIC, SEE VALUES IN |
| USP CATOLOG IN GRAY SHADING NO ADDITION- |
| AL STRESS ON STEEL CALCULATIONS. |
| 1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| |
| 18)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| S SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| MECH. 301.13 WIND RESISTANCE |
| MECHANICAL EQUIPMENT, APPLIANCES AND SUP |
| PORTS THAT ARE EXPOSED TO WIND SHALL BE |
| DESIGNED AND INSTALLED TO RESIST THE |
| WIND PRESSURES ON THE EQUIPMENT & THE |
| SUPPORTS AS DETERMINED IN ACCORDANCE |
| WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| LISHED BY DESIGN OR BY APPLICATION OF |
| SECTION 301.13.1. |
| |
| 19)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |