Plan Review Notes
Plan Review Notes For Permit 03120929
Permit Number 03120929
Review Stop P
Sequence Number 4
Notes
Date Text
2005-06-01 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1. PLANS ON FILE DO NOT SHOW A BADUJET
 SYSTEM. A REVISION IS REQUIRED SHOWING
 THE PUMP, ALL PIPING, A NEW PIPING
 SCHEMATIC, LOCATION OF THE PIPING ON THE
 POOL LAYOUT ECT. SECTION 104.2.1.
 2. THE CALCULATED VALUATION OF THE POOL
 SHALL BE ADJUSTED REFLECTING THE COST OF
 THE BADUJET SYSTEM AND ALL RELATED
 PIPING AND LABOR. PLEASE PROVIDE AN
 ADJUSTED CONTRACT SIGNED AND DATED BY
 THE OWNER OF THE PROPERTY. ALSO A
 REVISION FEE WILL BE DUE UPON SUBMITTING
 THE REVISION. SECTION 104.6.5.
 3. FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) SHOW DRAINS FOR BADUJET SYSTEM
 ON POOL LAYOUT. SECTION 104.2.1.
 4. FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) SHOW VENT FOR
 BADUJET SYSTEM, OR SHOW COMPLIANCE WITH
 ABOVE SECTION. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]