Plan Review Notes
Plan Review Notes For Permit 03120929
Permit Number 03120929
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) VENT REQUIRED FOR MAIN DRAINS IN THE
 VANISHING EDGE. SEC 424.2.6.6.3
  
 REVIEW BY KEN STEVENS