Plan Review Notes For Permit 03120894 |
Permit Number |
03120894 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-11-05 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE MASTER BEDROOM NEEDS A | | RECEPTACLE | | TO COMPLY WITH 210.52(A) 2002 NEC. | | | | 2} THE MASTER BATH RECEPTACLES MUST BE | | GFI PROTECTED PER 210.8(A)(2). | | | | 3} THE RECEPTACLE SPACING FOR KITCHEN | | CABINETS MUST COMPLY WITH 210.52(C)(1). | | | | 4} THE HALLWAY (GALLERY) TO BEDROOM #2 | | MUST HAVE A RECEPTACLE PER 210.52(H). | | THE AREA OF THIS SPACE HAS INCREASED | | SINCE THE LAST ELECTRICAL REVIEW AND | | NOW | | MUST COMPLY WITH THI SPACE REQUIREMENT. | | | | 5} THE RECEPTACLE NEXT TO THE PANELS IN | | THE GARAGE MUST BE GFI PER 210.8(A)(2). | | | | PLEASE IDENTIFY THE REVISIONS WITH SOME | | STANDARD MARKING SUCH AS CLOUDING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|