2004-11-05 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE MASTER BEDROOM NEEDS A
 RECEPTACLE
 TO COMPLY WITH 210.52(A) 2002 NEC.
  
 2} THE MASTER BATH RECEPTACLES MUST BE
 GFI PROTECTED PER 210.8(A)(2).
  
 3} THE RECEPTACLE SPACING FOR KITCHEN
 CABINETS MUST COMPLY WITH 210.52(C)(1).
  
 4} THE HALLWAY (GALLERY) TO BEDROOM #2
 MUST HAVE A RECEPTACLE PER 210.52(H).
 THE AREA OF THIS SPACE HAS INCREASED
 SINCE THE LAST ELECTRICAL REVIEW AND
 NOW
 MUST COMPLY WITH THI SPACE REQUIREMENT.
  
 5} THE RECEPTACLE NEXT TO THE PANELS IN
 THE GARAGE MUST BE GFI PER 210.8(A)(2).
  
 PLEASE IDENTIFY THE REVISIONS WITH SOME
 STANDARD MARKING SUCH AS CLOUDING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  