Date |
Text |
2004-03-10 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) THE SIZE OF THE ATTIC ACCESS DOES NOT |
| COMPLY WITH THE MINIMUM SPECIFIED BY |
| FBC 2309.6. (20" X 36" MINIMUM) |
| |
| 3) ON SHEET A2 FBD IS INCORRECTLY |
| SPECIFIED FOR FBC(FLORIDA BUILDING CODE) |
| PLEASE CORRECT. |
| |
| 4) 1001.1.3/ 1005.4 ZERO LOT LINE |
| EGRESS:WHEN ACCESS TO OR FROM A RE- |
| QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| ING OF A STRUCTURE TO THE PUBLIC WAY, |
| REQUIRES TRANSVERSING A PROPERTY |
| (ADJOINING LOT) THAT IS NOT PART OF THE |
| ONE WHICH THE STRUCTURE IS LOCATED, AN |
| EGRESS EASEMENT THROUGH THE ADJOINING |
| PROPERTY IS REQUIRED AND SHALL BE RECORD |
| ED IN THE COUNTY RECORDS. THIS EASEMENT |
| SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| ING SHALL BE PLACED WITHIN THE EASEMENT |
| AREA WHICH WOULD BLOCK ACCESS TO THE |
| EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| FROM THE RESCUE OPENING TO THE PUBLIC |
| WAY. NO LANDSCAPING, FENCES OR OTHER |
| IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| EASEMENT. SUBMIT A COPY OF THE RECORDED |
| SUBDIVISION COVENANTS SPECIFYING THE |
| ABOVE REQUIREMENTS. |
| |
| 5) THE FBC TABLE 600 CALCULATIONS FOR |
| THE EXTERIOR WALL AT THE DINING ROOM AND |
| DEN/STUDY ARE INCORRECT. SEE NOTES ON |
| THE PLAN. ONLY 20% OF THE WALL AREA |
| (64 SQFT) IS ALLOWED AS OPENINGS. PLEASE |
| CORRECT. |
| |
| 6) SUBMIT 2 COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS AND UL LISTING |
| INFORMATION FOR THE GAS BBQ AND HOOD. |
| |
| 7) INDICATE THAT THE 9,610# CAPACITY |
| LISTED FOR STEEL COLUMN SC-1 IS FOR |
| UPLIFT. |
| |
| 8) SPECIFY THE UPLIFT CAPACITY OF STEEL |
| COLUMN SC-2. |
| |
| 9) ON SHEET S-2 THE ARROW SPECIFYING THE |
| LOCATION FOR THE 4B CONNECTOR AT THE |
| RIGHT SIDE OF THE ENTRY IS INDICATING |
| THE WRONG PLACE. PLEASE CORRECT. |
| |
| 10) SPECIFY THE FASTENERS FOR CONNECTOR |
| 4B ON S4. INDICATE THE TYPE, DIAMETER |
| AND LENGTH/EMBED DEPTH. |
| |
| 11) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| SUBMIT STATE OR LOCAL PRODUCT APPROVALS |
| FOR THE FOLLOWING: |
| - DOUBLE INSWING ENTRY DOORS |
| - DOUBLE OUTSWING GLAZED DOORS WITH AND |
| WITHOUT SIDELITES |
| - SINGLE OUTSWING PANEL DOORS |
| - SINGLE HUNG WINDOWS |
| - FIXED GLASS WINDOWS (CIRCULAR,ARCHED, |
| ETC.) |
| - GLASS BLOCK (ONE HOUR FIRE RATED) |
| - STRUCTURAL MULLIONS |
| - OVERHEAD GARAGE DOORS |
| - STORM PANELS |
| |
| 12) SUBMIT MANUFACTURER'S INSTALLATION |
| SPECIFICATIONS AND LISTING FOR ONE HOUR |
| FIRE RATED GLASS BLOCK. |
| |
| 13) SUBMIT AN INSTALLATION SCHEDULE AND |
| KEY PLAN FOR THE STORM PANELS. SPECIFY |
| THE MOUNT TYPE, ANCHOR TYPE AND SPACING |
| ON THE INSTALLATION DRAWINGS. |
| |
| 14) A SEPARATE PERMIT WILL BE REQUIRED |
| FOR ROOFING. ROOFING CONTRACTOR HAD NOT |
| SIGNED THE PERMIT AT TIME OF APPLICATION |
| |
| SUBMIT (2) COPIES OF ALL ITEMS REQUESTED |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |