2004-02-17 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT A SIGNED AND SEALED COPY OF |
| THE SOIL REPORT, INCLUDING BORING LOGS. |
| |
| 4) THE SIZE OF THE ATTIC ACCESS DOES NOT |
| COMPLY WITH THE MINIMUM SPECIFIED BY |
| FBC 2309.6. |
| |
| 5) 1001.1.3/ 1005.4 ZERO LOT LINE |
| EGRESS:WHEN ACCESS TO OR FROM A RE- |
| QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| ING OF A STRUCTURE TO THE PUBLIC WAY, |
| REQUIRES TRANSVERSING A PROPERTY |
| (ADJOINING LOT) THAT IS NOT PART OF THE |
| ONE WHICH THE STRUCTURE IS LOCATED, AN |
| EGRESS EASEMENT THROUGH THE ADJOINING |
| PROPERTY IS REQUIRED AND SHALL BE RECORD |
| ED IN THE COUNTY RECORDS. THIS EASEMENT |
| SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| ING SHALL BE PLACED WITHIN THE EASEMENT |
| AREA WHICH WOULD BLOCK ACCESS TO THE |
| EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| FROM THE RESCUE OPENING TO THE PUBLIC |
| WAY. NO LANDSCAPING, FENCES OR OTHER |
| IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| EASEMENT. DUE TO THE RIGHT SIDE OF THE |
| STRUCTURE BEING 8 INCHES FROM THE |
| PROPERTY LINE, AN EGRESS ESAEMENT IS |
| REQUIRED. SUBMIT A COPY OF THE SUB- |
| DIVISION COVENENTS SPECIFYING THIS. |
| |
| 6) PROVIDE TABLE 600 CALCULATIONS FOR |
| THE EXTERIOR WALL OF THE DINING ROOM AND |
| DEN/STUDY AT THE GARDEN COURT, WHICH HAS |
| 20% OF THE WALL AREA ALLOWED AS OPENINGS |
| |
| 7) SPECIFY THE SIZE OF THE FRENCH DOOR |
| SIDELITES IN THE DINING ROOM. |
| |
| 8) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| AND UL OR OTHER LISTING INFORMATION FOR |
| THE BBQ AND HOOD SPECIFIED AT THE |
| COVERED PORCH. |
| |
| 9) SPECIFY THE UPLIFT THAT THE STEEL |
| COLUMN ON SHEET S4 IS CAPABLE OF |
| RESISTING. |
| |
| 10) 1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREASE IN ALLOWABLE STRESS |
| SPECIFIED IN THE MATERIALS SECTION OF |
| THE CODE OR A REFRENCED STANDARD SHALL |
| NOT BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. REVISE THE TRUSS ANCHOR |
| SCHEDULE TO VALUES THAT DO NOT INCLUDE |
| A ONE-THIRD INCREASE IN THE STEEL |
| CALCULATIONS. UPDATE ANCHORS TO THOSE |
| WITH STATE OF FLORIDA PRODUCT APPROVAL |
| AS REQUIRED BY RULE 9B-72. CORRECT |
| CONNECTORS THAT ARE SPECIFIED ON SHEET |
| S2 FOR INDICATED UPLIFTS WHICH EXCEED |
| THE UPLIFT CAPACITIES LISTED IN THE |
| SCHEDULE ON S3. |
| |
| 10) SPECIFY THE CONNECTORS/HANGERS FOR |
| THE CONNECTION OF THE 2X BEAMS TO THE |
| WALL OF THE STRUCTURE AT THE ENTRY. |
| |
| 11)PROVIDE A DETAIL OF THE STEEL COLUMNS |
| CARRYING THE 2X BEAMS AT THE ENTRY |
| WHICH MEET AT 90 DEGREE ANGLES ON THESE |
| COLUMNS. |
| |
| 12) THE ROOF FRAMING PLAN ON S2 DOES NOT |
| CORRESPOND WITH THE OTHER PLANS FOR THE |
| LOCATIONS OF THE 2X BEAMS AT THE ENTRY. |
| PLEASE CORRECT. |
| |
| 13) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| SUBMIT STATE OR LOCAL PRODUCT APPROVALS |
| FOR THE FOLLOWING: |
| - DOUBLE INSWING ENTRY DOORS |
| - DOUBLE OUTSWING GLAZED DOORS WITH AND |
| WITHOUT SIDELITES. |
| - SINGLE OUTSWING PANEL DOORS |
| - SINGLE HUNG WINDOWS |
| - FIXED GLASS WINDOWS (CIRCULAR,ARCHED, |
| ETC.) |
| - GLASS BLOCK (FIRE RATED) |
| - STRUCTURAL MULLIONS |
| - OVERHEAD GARAGE DOORS |
| - STORM PANELS |
| - TRUSS ANCHORS AND CONNECTORS |
| |
| 14) SUBMIT MANUFACTURER'S INSTALLATION |
| SPECIFICATIONS AND LISTING FOR ONE HOUR |
| FIRE RATED GLASS BLOCK ASSEMBLY. |
| |
| 15) IF STORM PANELS WILL BE USED, SUBMIT |
| A KEY PLAN AND INSTALLATION SCHEDULE. |
| SPECIFY THE MOUNT TYPE, ANCHOR TYPE AND |
| SPACING ON THE INSTALLATION DRAWINGS. |
| |
| 16) A SEPARATE PERMIT WILL BE REQUIRED |
| FOR ROOFING. ROOFING CONTRACTOR DID NOT |
| SIGN THE APPLICATION. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |