2003-12-23 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE PROVIDE THE FOLLOWING |
| INFORMATION MAKE NECESSARY CORRECTIONS |
| TO THE DRAWINGS AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110.9. |
| |
| 2} THE EQUIPMENT GROUND BEING RAN FROM |
| THE METER TO THE DISCONNECT CREATES A |
| PARALLEL FAULT RETURN PATH WITH THE |
| NEUTRAL AND MUST NOT BE INSTALLED PER |
| 250.6(B). |
| |
| 3} PLEASE PROVIDE A LOAD CALCULATION PER |
| 220 SECTION 2 OR 220.30 SO TO SHOW |
| COMPLIANCE WITH THE CORRECT VA RATINGS |
| REQUIRED BY THIS ARTICLE. |
| |
| 4} NOTE THAT THE WATER HEATER IS SHOWN |
| ON THE PANEL SCHEDULE AS DRAWING 19 |
| AMPS, PLEASE CLARIFY. |
| |
| 5} NOTE #9 CALLS FOR ALL CONDUCTORS TO |
| BE #12,ALL THE WIRE LISTED ON PANEL "B" |
| IS #14,PLEASE CORRELATE. |
| |
| 6} PLEASE SHOW THE LOCATION OF THE |
| SERVICE EQUIPMENT(METER & MAIN |
| DISCONNECT). |
| |
| 7} PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S). PER 210.11-C-3 |
| MUST BE 20A AND #12AWG,INCLUDING THE |
| POOL BATH AND POWDER ROOM. |
| |
| 8} THE LOCATION OF THE RECEPTACLE IN THE |
| MASTER BATH DOES NOT COMPLY WITH |
| 210.52(D)-3'. |
| |
| 9} 210.12 REGARDING BEDROOM OUTLETS ALSO |
| APPLIES TO SMOKE DETECTORS AND |
| LIGHTS/FANS,PLEASE MAKE THE APPROPRIATE |
| NOTES TO PLANS. |
| |
| 10} PLEASE NOTE FRONT AND REAR |
| RECEPTS REQ'D PER 210.52E |
| |
| 11} PLEASE NOTE KITCHEN COUNTER- |
| SPACE RECEPT SPACING SHALL MEET ART; |
| 210.52C 1,2,3,4,AND 5. |
| |
| 12} BEDROOM #3 IS MISSING A RECEPTACLE |
| NEEDED TO COMPLY WITH 210.52(A)(1). |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718. |