Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE NECESSARY CORRECTIONS
 TO THE DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 2} THE EQUIPMENT GROUND BEING RAN FROM
 THE METER TO THE DISCONNECT CREATES A
 PARALLEL FAULT RETURN PATH WITH THE
 NEUTRAL AND MUST NOT BE INSTALLED PER
 250.6(B).
  
 3} PLEASE PROVIDE A LOAD CALCULATION PER
 220 SECTION 2 OR 220.30 SO TO SHOW
 COMPLIANCE WITH THE CORRECT VA RATINGS
 REQUIRED BY THIS ARTICLE.
  
 4} NOTE THAT THE WATER HEATER IS SHOWN
 ON THE PANEL SCHEDULE AS DRAWING 19
 AMPS, PLEASE CLARIFY.
  
 5} NOTE #9 CALLS FOR ALL CONDUCTORS TO
 BE #12,ALL THE WIRE LISTED ON PANEL "B"
 IS #14,PLEASE CORRELATE.
  
 6} PLEASE SHOW THE LOCATION OF THE
 SERVICE EQUIPMENT(METER & MAIN
 DISCONNECT).
  
 7} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210.11-C-3
 MUST BE 20A AND #12AWG,INCLUDING THE
 POOL BATH AND POWDER ROOM.
  
 8} THE LOCATION OF THE RECEPTACLE IN THE
 MASTER BATH DOES NOT COMPLY WITH
 210.52(D)-3'.
  
 9} 210.12 REGARDING BEDROOM OUTLETS ALSO
 APPLIES TO SMOKE DETECTORS AND
 LIGHTS/FANS,PLEASE MAKE THE APPROPRIATE
 NOTES TO PLANS.
  
 10} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210.52E
  
 11} PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPT SPACING SHALL MEET ART;
 210.52C 1,2,3,4,AND 5.
  
 12} BEDROOM #3 IS MISSING A RECEPTACLE
 NEEDED TO COMPLY WITH 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.