Date |
Text |
2004-02-24 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) FROM PREVIOUS REVIEW:2 COMMENTS |
| (3) TOILET ROOM SHALL BE ACCESSIBLE PER |
| 11-4.1.2(6). SUBMIT DETAILS FOR FIXTURES |
| PER 11-4.16 WATER CLOSET, 11-4.19 LAV., |
| AND 11-4.22 TOILET ROOM. SHOW CLEAR |
| FLOOR SPACE FOR FIXTURES, GRAB BAR |
| HEIGHT, LAV HEIGHT AND CLEARANCES, |
| TOILET HEIGHT, EXPOSED PIPES AND SURFAC- |
| ES FOR LAV. ECT. INDICATE INTERIOR |
| MEASUREMENTS FOR TOILET ROOM. |
| (8) PER TABLE 403.1 A DRINKING FOUNTAIN |
| IS REQUIRED. (ALSO SEE SECTION 410.1) |
| **********NEW COMMENTS********** |
| 1B) SHT 5 SANITARY RISER DIAGRAM: THE |
| THREE COMPARTMENT SINK SHALL DRAIN INTO |
| THE FLOOR SINK. IT IS TIED INTO THE SAN- |
| ITARY BRANCH LINE DIRECTLY. A SAMPLE |
| POINT IS REQUIRED PRIOR TO THE TOILET |
| ROOM ON THE SANITARY RISER DIAGRAM. |
| 2B) SUBMIT A WATER RISER DIAGRAM REQUIR- |
| ED PER SECTION 104.3.1.1. |
| 3B) INFORMATIONAL: DEPT OF AGRICULTURE |
| & CONSUMER SERVICES SHALL BE REQUIRED |
| TO BE NOTIFIED PRIOR TO OPENING. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |