Plan Review Notes
Plan Review Notes For Permit 03120826
Permit Number 03120826
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW:2 COMMENTS
 (3) TOILET ROOM SHALL BE ACCESSIBLE PER
 11-4.1.2(6). SUBMIT DETAILS FOR FIXTURES
 PER 11-4.16 WATER CLOSET, 11-4.19 LAV.,
 AND 11-4.22 TOILET ROOM. SHOW CLEAR
 FLOOR SPACE FOR FIXTURES, GRAB BAR
 HEIGHT, LAV HEIGHT AND CLEARANCES,
 TOILET HEIGHT, EXPOSED PIPES AND SURFAC-
 ES FOR LAV. ECT. INDICATE INTERIOR
 MEASUREMENTS FOR TOILET ROOM.
 (8) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. (ALSO SEE SECTION 410.1)
 **********NEW COMMENTS**********
 1B) SHT 5 SANITARY RISER DIAGRAM: THE
 THREE COMPARTMENT SINK SHALL DRAIN INTO
 THE FLOOR SINK. IT IS TIED INTO THE SAN-
 ITARY BRANCH LINE DIRECTLY. A SAMPLE
 POINT IS REQUIRED PRIOR TO THE TOILET
 ROOM ON THE SANITARY RISER DIAGRAM.
 2B) SUBMIT A WATER RISER DIAGRAM REQUIR-
 ED PER SECTION 104.3.1.1.
 3B) INFORMATIONAL: DEPT OF AGRICULTURE
 & CONSUMER SERVICES SHALL BE REQUIRED
 TO BE NOTIFIED PRIOR TO OPENING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved