Plan Review Notes
Plan Review Notes For Permit 03120826
Permit Number 03120826
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) PERMIT FOR PLUMBING CAN NOT BE ISSUED
 PRIOR TO CLAIRFICATION OF PREVIOUS OCC-
 UPANCY FOR SPACE. MORE COMMENTS MAY NEED
 TO BE ADDRESSED ACCORDING TO RESPONSE.
 OTHER PLAN REVIEWS MAY BE REQUIRED BY
 BLDG., FIRE, ELECT., & MECH. 104.2.1.2
 2) FIRE DEPT PLAN REVIEW REQUIRED FOR
 NEW RESTURANT. 104.3.1.1(7).
 3) TOILET ROOM SHALL BE ACCESSIBLE PER
 11-4.1.2(6). SUBMIT DETAIL FOR FIXTURES
 PER 11-4.16 WATER CLOSET, 11-4.19 LAV.,
 AND 11-4.22 TOILET ROOM. SHOW CLEAR
 FLOOR SPACE, TURNING AREA, AND ALL SUB-
 SECTIONS OF ABOVE SECTIONS FOR COMPLIAN-
 CE. INDICATE INTERIOR MEASUREMENTS FOR
 TOILET ROOM.
 4) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION, HOTEL AND BUSINESS DIVISION.
 101.4.7
 5) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZE OF GREASE INTERCEPT-
 OR. WASTE ORD. 2938-96. (561) 837-4074.
 6) SHT 2 OF 5 GREASE TRAP NOT ALLOWED
 UNDER SINK. (SEE COMMENT #5)
 7) HAND SINK NOT SHOWN ON FLOOR PLAN.
 PLEASE SHOW HAND SINK. 104.2.1
 8) PER TABLE 403.1 A DRINKING FOUNTAIN &
 A SERVICE SINK ARE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]