Date |
Text |
2003-12-29 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) PERMIT FOR PLUMBING CAN NOT BE ISSUED |
| PRIOR TO CLAIRFICATION OF PREVIOUS OCC- |
| UPANCY FOR SPACE. MORE COMMENTS MAY NEED |
| TO BE ADDRESSED ACCORDING TO RESPONSE. |
| OTHER PLAN REVIEWS MAY BE REQUIRED BY |
| BLDG., FIRE, ELECT., & MECH. 104.2.1.2 |
| 2) FIRE DEPT PLAN REVIEW REQUIRED FOR |
| NEW RESTURANT. 104.3.1.1(7). |
| 3) TOILET ROOM SHALL BE ACCESSIBLE PER |
| 11-4.1.2(6). SUBMIT DETAIL FOR FIXTURES |
| PER 11-4.16 WATER CLOSET, 11-4.19 LAV., |
| AND 11-4.22 TOILET ROOM. SHOW CLEAR |
| FLOOR SPACE, TURNING AREA, AND ALL SUB- |
| SECTIONS OF ABOVE SECTIONS FOR COMPLIAN- |
| CE. INDICATE INTERIOR MEASUREMENTS FOR |
| TOILET ROOM. |
| 4) ROUTE PLANS TO THE DEPT. OF BUSINESS |
| REGULATION, HOTEL AND BUSINESS DIVISION. |
| 101.4.7 |
| 5) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| COMPLIANCE FOR SIZE OF GREASE INTERCEPT- |
| OR. WASTE ORD. 2938-96. (561) 837-4074. |
| 6) SHT 2 OF 5 GREASE TRAP NOT ALLOWED |
| UNDER SINK. (SEE COMMENT #5) |
| 7) HAND SINK NOT SHOWN ON FLOOR PLAN. |
| PLEASE SHOW HAND SINK. 104.2.1 |
| 8) PER TABLE 403.1 A DRINKING FOUNTAIN & |
| A SERVICE SINK ARE REQUIRED. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |