Plan Review Notes For Permit 03120783 |
Permit Number |
03120783 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-02-11 00:00:00 | DENIED:2ND REQUEST | | REFERENCE COMMENTS BY HAROLD MOSER DATED | | 1-14-04: | | 1.PLANS DO NOT INDICATE AN AUXILIARY | | DRAIN PAN.DRAIN PAN IS REQUIRED PER | | 2001 FBC(M) 307.2.3.OVERFLOW DRAIN | | SHALL TERMINATE AT A CONSPICUOUS POINT. | | PLANS INDICATE OVERFLOW TERMINATING AT | | THE SAME POINT AS THE PRIMARY DRAIN | | WHICH IS NOT A CONSPICUOUS POINT. PLEASE | | REVISE PLANS TO INDICATE DRAIN PAN AND | | OVERFLOW TERMINATING AT A CONSPICUOUS | | POINT. (OVER A SINK, SHOWER, TOILET).A | | FLOAT SWITCH MAY BE USED IN LIEU OF | | AUXILIARY DRAIN. | | | | 2.RETURN AIR NOT SIZED PROPERLY.SEE | | THE ATTACHED SCHEDULE INDICATING PROPER | | SIZING.PLEASE NOTE ALL SUPPLY AIR TO | | THE MASTER SUITE IS TO BE INCLUDED IN | | THE CALCULATION FOR TOTAL SUPPLY AIR TO | | THAT SPACE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|