Plan Review Notes For Permit 03120783 |
Permit Number |
03120783 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-06 00:00:00 | *************** UNSAT *********** | | | | 1)NOTE: PLEASE SEE CHAPETR 34 FBC, | | PLEASE SEE THAT ALL EXISTING ELECTRICAL | | WILL BE REQ'D TO BROUGHT UP TO CODE. | | PLEASE SHOW "EXISTING" AND ANY NEW THAT | | MAY NEED TO BE BROUGHT UP. | | SD'S ARE NOTED ON PLANS, HOWEVER ALL | | EXISTING BEDROOMS WILL BE REQ'D TO BE | | ARC FAULT PROTECTED. 210.12 | | EXISTING BATH(S) CIRCUITS ETC. 210.11C3 | | ETC, | | | | 2)NOTE; PLEASE SEE MISSING RECEPT FOR | | 2' OF WALL. PER 210.52 | | | | 3)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS | | ON ELECTRICAL PLANS. | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATINGS | | FOR ALL NEW SERVICE EQUIPMENT BEING | | INSTALLED. PER 110.9 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | SECOND SET OF PLANS ARE REQ'D TO BE SIGN | | -ED, DATED AND SEALED. PER FS 481.221 | | PLANS ARE SIGNED BUT NOT SEALED. |
|