2004-03-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} AN EQUIPMENT GROUND PER 250.122 IS
 REQUIRED FROM PANEL "A" TO THE SUB-
 PANEL.
  
 2} THE SUB PANEL FEEDER ON THE PANEL"A"
 SCHEDULE IS LISTED AS #14 ON A 15AMP
 SINGLE POLE BREAKER. THE PREVIOUSLY
 SUBMITTED PLAN WAS RETURNED TO THE
 ARCHITECT WITH A COMMENT ABOUT THIS
 FEEDER BEING A 2 POLE 20AMP. PEASE
 INDICATE THE CORRECT OCP AND FEEDER
 SIZE ON PLANS.
  
 3} VERIFY THE LOCATION OF THE POOL
 PANEL(SUB PANEL).
  