Plan Review Notes
Plan Review Notes For Permit 03120422
Permit Number 03120422
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-23 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE ORIGINAL REDLINED
 NOTES.
 PLEASE CORRELATE PANEL SCHEDULES WITH
 RISER DIAGRAM. 200A PANEL SHOWS A 2P20A
 BRKR FEEDING 60A SUB PANEL?
 PLEASE SEE LOAD.
  
 2)NOTE: PLEASE REVISE LOAD CALCULATIONS
 TO INCLUDE NEW LOADS.
 LOADS WERE NOT ADDED TO 200A PANEL/SERV.
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM 200A PANEL
 TO 60A SUB PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]