Plan Review Notes
Plan Review Notes For Permit 03120348
Permit Number 03120348
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-23 00:00:00**************DENIED********************
 FLOW DATA CALCULATION FOR THE SAFETY
 MARGIN IS 2.194 WEST PALM BEACH REQUIRES
 A SAFETY MARGIN 5 PSI MINIMUM.
  
 ALSO THE FIRST SPRINKLER CONTRACTOR AND
 THIS OFFICE REVIEWED PROJECT AND THERE
 WERE SPRINKLER COVERAGE PROBLEMS
 REGARDING LIGHT FIXTURES, RAFTERS AND
 BEAMS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910