Plan Review Notes
Plan Review Notes For Permit 03120231
Permit Number 03120231
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/16/03:
  
 1) FBC 1606.1DESIGN WIND SPEED.IT IS
 NOTED THAT THE SUBMITTED DESIGN
 CALCULATIONS BY HI-TRANS ENGINEERING INC
 ARE BASED ON A DESIGN WIND SPEED OF
 140 MPH BUT PLAN SHEET 8, NOTE 13, STILL
 STATES "...LIGHT POLE INSTALLATONS SHALL
 BE SUITABLE FOR 110 MPH".THE DESIGN
 WIND SPEED FOR THE CITY OF WEST PALM
 BEACH IS 140 MPH.AMEND SHEET 8.
  
 2) 471.003(2)(I) F.S.SHEET 8 INCLUDES
 STRUCTURAL DETAILS AND SHALL BE SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER.
 NOTE:
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]