2004-01-20 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 12/16/03: |
| |
| 1) FBC 1606.1DESIGN WIND SPEED.IT IS |
| NOTED THAT THE SUBMITTED DESIGN |
| CALCULATIONS BY HI-TRANS ENGINEERING INC |
| ARE BASED ON A DESIGN WIND SPEED OF |
| 140 MPH BUT PLAN SHEET 8, NOTE 13, STILL |
| STATES "...LIGHT POLE INSTALLATONS SHALL |
| BE SUITABLE FOR 110 MPH".THE DESIGN |
| WIND SPEED FOR THE CITY OF WEST PALM |
| BEACH IS 140 MPH.AMEND SHEET 8. |
| |
| 2) 471.003(2)(I) F.S.SHEET 8 INCLUDES |
| STRUCTURAL DETAILS AND SHALL BE SIGNED |
| AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER. |
| NOTE: |
| PLANS SIGNED & SEALED BY A PROFESSIONAL |
| ENGINEER SHALL INCLUDE EITHER THE NAME, |
| ADDRESS AND LICENSE NUMBER OF THE |
| ENGINEER OR, THE NAME AND LICENSE NUMBER |
| OF THE ENGINEER AND THE NAME, ADDRESS |
| AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS THROUGH |
| WHICH THE ENGINEER IS PRACTICING |
| (471.025 F.S. AND 471.023 F.S.). |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |