Plan Review Notes
Plan Review Notes For Permit 03120203
Permit Number 03120203
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-29 00:00:001) THE FIRE ALARM SYSTEM IS TO REMAIN
 FUNCTIONAL WHILE THE NEW SYSTEM IS
 BEING INSTALLED. THE HOSPITAL SHALL BE
 PROTECTED AT ALL TIMES BY AN
 OPERATIONAL FIRE ALARM SYSTEM. EXISTING
 INITIATING DEVICES SHALL REMAIN
 OPERATIONAL.
  
 2) THE ENTIRE NEW FIRE ALARM SYSTEM
 SINCE INSTALLATION AND COMPLETION
 WILL OCCUR AFTER AUGUST 1, 2003 SHALL
 BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 3) NEW FIRE ALARM SYSTEM SHALL BE
 CLASS A OR FULLY ADDRESSABLE.
  
 4) ALL SMOKE DETECTORS SHALL BE MOUNTED
 A MINIMUM OF THREE FEET FROM AIR
 CONDITIONING DIFFUSERS.
  
 5) BEFORE A DECISION WILL BE MADE
 REGARDING THE INSTALLATION OF STROBES
 IN INDIVIDUAL BATHROOMS OF TREATMENT
 ROOMS. A BATHROOM COUNT WILL BE
 REQUIRED. PLEASE INDICATE GENERAL
 OCCUPANCY PER FLOOR AND TOTAL BATHROOMS
 IN PT. TREATMENT ROOMS.
  
 6) KITCHEN ANSUL SYSTEM(S) ARE REQUIRED
 TO BE CONNECTED TO THE FIRE ALARM
 SYSTEMS.
  
 7) PLEASE PROVIDE A COPY OF THE SIGNED
 CONTRACT. THE VALUE LISTED ON PERMIT
 APPLICATION APPEARS LOW. PLEASE PROVIDE
 A COPY OF THE CONTRACT DISPLAYING
 LABOR COSTS AND MATERIALS.
  
 8) ENSURE THAT ENOUGH REMOTE
 ANNUNCIATORS ARE INSTALLED ON THE
 HOSPITAL CAMPUS.
  
 9) WHO IS RESPONSIBLE FOR PATCHING
 HOLES IN RATED WALLS AND FLOORS.
  
 10) SECURITY DEVICES ON EXIT DOORS
 SHALL MEET ALL REQUIREMENTS OF THE
 FIRE CODE.
  
 11) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE WILL SAY. PLEASE
 NOTE THIS ON THE PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910