2003-12-29 00:00:00 | 1) THE FIRE ALARM SYSTEM IS TO REMAIN |
| FUNCTIONAL WHILE THE NEW SYSTEM IS |
| BEING INSTALLED. THE HOSPITAL SHALL BE |
| PROTECTED AT ALL TIMES BY AN |
| OPERATIONAL FIRE ALARM SYSTEM. EXISTING |
| INITIATING DEVICES SHALL REMAIN |
| OPERATIONAL. |
| |
| 2) THE ENTIRE NEW FIRE ALARM SYSTEM |
| SINCE INSTALLATION AND COMPLETION |
| WILL OCCUR AFTER AUGUST 1, 2003 SHALL |
| BE UL LISTED FOR CENTRAL STATION |
| SERVICE. |
| |
| 3) NEW FIRE ALARM SYSTEM SHALL BE |
| CLASS A OR FULLY ADDRESSABLE. |
| |
| 4) ALL SMOKE DETECTORS SHALL BE MOUNTED |
| A MINIMUM OF THREE FEET FROM AIR |
| CONDITIONING DIFFUSERS. |
| |
| 5) BEFORE A DECISION WILL BE MADE |
| REGARDING THE INSTALLATION OF STROBES |
| IN INDIVIDUAL BATHROOMS OF TREATMENT |
| ROOMS. A BATHROOM COUNT WILL BE |
| REQUIRED. PLEASE INDICATE GENERAL |
| OCCUPANCY PER FLOOR AND TOTAL BATHROOMS |
| IN PT. TREATMENT ROOMS. |
| |
| 6) KITCHEN ANSUL SYSTEM(S) ARE REQUIRED |
| TO BE CONNECTED TO THE FIRE ALARM |
| SYSTEMS. |
| |
| 7) PLEASE PROVIDE A COPY OF THE SIGNED |
| CONTRACT. THE VALUE LISTED ON PERMIT |
| APPLICATION APPEARS LOW. PLEASE PROVIDE |
| A COPY OF THE CONTRACT DISPLAYING |
| LABOR COSTS AND MATERIALS. |
| |
| 8) ENSURE THAT ENOUGH REMOTE |
| ANNUNCIATORS ARE INSTALLED ON THE |
| HOSPITAL CAMPUS. |
| |
| 9) WHO IS RESPONSIBLE FOR PATCHING |
| HOLES IN RATED WALLS AND FLOORS. |
| |
| 10) SECURITY DEVICES ON EXIT DOORS |
| SHALL MEET ALL REQUIREMENTS OF THE |
| FIRE CODE. |
| |
| 11) PLEASE INDICATE WHAT THE VOICE |
| EVACUATION MESSAGE WILL SAY. PLEASE |
| NOTE THIS ON THE PLAN. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |