2003-12-18 00:00:001) NOTE # 29 ON TITLE PAGE IS INCORRECT.
 STANDPIPES ARE REQUIRED TO BE ERECTED
 AFTER CONSTRUCTION HAS PROGRESSED ABOVE
 30 FEET. PLEASE REVISE PLANS AS
 NECESSARY.
  
 2) THE ENTIRE BUILDING IS REQUIRED TO
 BE COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL MECHANICAL,
 ELECTRICAL, AND TELEPHONE ROOMS. THE
 TOP OF ALL STAIRS AND OTHER SHAFTS ARE
 ALSO REQUIRED TO BE FIRE SPRINKLER
 PROTECTED.
  
 3) ALL VOID OR DEAD SPACES SHALL BE FIRE
 SPRINKLER PROTECTED UNLESS WRITTEN
 VERIFICATION IS RECEIVED THAT THERE WILL
 BE NO ACCESS AND NO STORAGE PRESENT
 IN THESE AREAS.
  
 4) NO FIRE SPRINKLER PROTECTION SHOWN
 FOR FIRE PUMP ROOM OR STORAGE ROOM
 ON FP-2.
  
 5) SINCE THE BUILDING IS A HIGH-RISE
 TWO FIRE DEPARTMENT CONNECTIONS WILL
 BE REQUIRED. AT LEAST ONE OF THESE
 CONNECTIONS SHALL BE LOCATED WITHIN
 150 FEET OF A FIRE HYDRANT.
  
 6) NO FIRE SPRINKLER PROTECTION IN
 ELEVATOR MACHINE ROOM # 5 ON PAGE FP-2.
  
 7) NO FIRE SPRINKLER PROTECTION NOTED
 IN SMALL ROOM WITH DOUBLE DOORS
 LOCATED IN STORAGE ROOM ON PAGE FP-3.
  
 8) NO FIRE SPRINKLER PROTECTION SHOWN
 IN SEVERAL METER ROOMS.
  
 9) NO FIRE SPRINKLER PROTECTION SHOWN
 IN ELEVATOR VESTIBULE 3 & 4 ON PAGE
 FP-11, FLOORS 11-16, TOWER.
  
 10) PLEASE DOCUMENT ON PLANS THE CODE
 SECTION THAT ALLOWS FOR THE DELETION
 OF AUTOMATIC FIRE SPRINKLER PROTECTION
 FROM RESIDENTIAL BATHROOMS AND CLOSETS.
  
 11) THERE APPEARS TO BE NO FIRE
 SPRINKLER IN RESIDENTIAL BATHROOMS
 AND CLOSETS. PLEASE DOCUMENT REASON
 ON PLANS.
  
 12) THERE APPEARS TO BE NO FIRE
 SPRINKLER PROTECTION IN STORAGE ROOM
 FP-11.
  
 13) SEVERAL A/C AND WH AREAS ARE NOT
 PROTECTED ON PAGE FP-10.
  
 14) PLEASE SHOW A TYPICAL ELEVATION
 DETAIL OF A TYPICAL TRASH CHUTE FIRE
 SPRINKLER ARRANGEMENT.
  
 15) PLEASE CLEARLY ILLUSTRATE STANDPIPE
 SYSTEMS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL