Date |
Text |
2003-12-18 00:00:00 | 1) NOTE # 29 ON TITLE PAGE IS INCORRECT. |
| STANDPIPES ARE REQUIRED TO BE ERECTED |
| AFTER CONSTRUCTION HAS PROGRESSED ABOVE |
| 30 FEET. PLEASE REVISE PLANS AS |
| NECESSARY. |
| |
| 2) THE ENTIRE BUILDING IS REQUIRED TO |
| BE COMPLETELY FIRE SPRINKLER PROTECTED. |
| THIS INCLUDES ALL MECHANICAL, |
| ELECTRICAL, AND TELEPHONE ROOMS. THE |
| TOP OF ALL STAIRS AND OTHER SHAFTS ARE |
| ALSO REQUIRED TO BE FIRE SPRINKLER |
| PROTECTED. |
| |
| 3) ALL VOID OR DEAD SPACES SHALL BE FIRE |
| SPRINKLER PROTECTED UNLESS WRITTEN |
| VERIFICATION IS RECEIVED THAT THERE WILL |
| BE NO ACCESS AND NO STORAGE PRESENT |
| IN THESE AREAS. |
| |
| 4) NO FIRE SPRINKLER PROTECTION SHOWN |
| FOR FIRE PUMP ROOM OR STORAGE ROOM |
| ON FP-2. |
| |
| 5) SINCE THE BUILDING IS A HIGH-RISE |
| TWO FIRE DEPARTMENT CONNECTIONS WILL |
| BE REQUIRED. AT LEAST ONE OF THESE |
| CONNECTIONS SHALL BE LOCATED WITHIN |
| 150 FEET OF A FIRE HYDRANT. |
| |
| 6) NO FIRE SPRINKLER PROTECTION IN |
| ELEVATOR MACHINE ROOM # 5 ON PAGE FP-2. |
| |
| 7) NO FIRE SPRINKLER PROTECTION NOTED |
| IN SMALL ROOM WITH DOUBLE DOORS |
| LOCATED IN STORAGE ROOM ON PAGE FP-3. |
| |
| 8) NO FIRE SPRINKLER PROTECTION SHOWN |
| IN SEVERAL METER ROOMS. |
| |
| 9) NO FIRE SPRINKLER PROTECTION SHOWN |
| IN ELEVATOR VESTIBULE 3 & 4 ON PAGE |
| FP-11, FLOORS 11-16, TOWER. |
| |
| 10) PLEASE DOCUMENT ON PLANS THE CODE |
| SECTION THAT ALLOWS FOR THE DELETION |
| OF AUTOMATIC FIRE SPRINKLER PROTECTION |
| FROM RESIDENTIAL BATHROOMS AND CLOSETS. |
| |
| 11) THERE APPEARS TO BE NO FIRE |
| SPRINKLER IN RESIDENTIAL BATHROOMS |
| AND CLOSETS. PLEASE DOCUMENT REASON |
| ON PLANS. |
| |
| 12) THERE APPEARS TO BE NO FIRE |
| SPRINKLER PROTECTION IN STORAGE ROOM |
| FP-11. |
| |
| 13) SEVERAL A/C AND WH AREAS ARE NOT |
| PROTECTED ON PAGE FP-10. |
| |
| 14) PLEASE SHOW A TYPICAL ELEVATION |
| DETAIL OF A TYPICAL TRASH CHUTE FIRE |
| SPRINKLER ARRANGEMENT. |
| |
| 15) PLEASE CLEARLY ILLUSTRATE STANDPIPE |
| SYSTEMS. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |