2004-01-03 00:00:00 | *****PROVISO****** |
| |
| SUBMIT REVISIONS BEFORE FRAMING |
| INSPECTION. |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 |
| |
| 1.)THE GIRDER/WALL CONNECTION (SHEET |
| 3) SPECIFIES HUGHES CONNECTORS; HUGHES |
| IS NO LONGER IN BUSINESS. |
| |
| 2.)THE WOOD CONSTRUCTION NOTES, ITEM |
| #4, REFERS TO FBC3218.17.NOT IN THE |
| FBC CODE BOOK. |
| |
| 3.)HHGT1 AND HHGT2, CONNECTOR KST260 |
| SHEET RF1, NAILING CONFLICTS WITH THE |
| CATALOG AND DESIGN UPLIFT ON THE PLAN |
| EXCEEDS MAX ALLOWED BY THE CATALOG |
| (USE THE GREY BAR WITHOUT STRESS |
| INCREASE FOR STEEL, USP 2003 CATALOG). |
| |
| 4.)WOOD-TO-WOOD CONNECTORS ARE |
| SPECIFIED IN WOOD-TO-MASONRY |
| APPLICATIONS; FOR EXAMPLE, USP HTW. |
| ADDRESS. (SHEET RF1). |
| |
| 5.)PROVIDE A FIREBLOCK DETAIL FOR THE |
| DROPPED CEILINGS/SOFFITS, FBC705.3, |
| 2305.1.4. |
| |
| 6.)PROVIDE STATEWIDE OR SITE SPECIFIC |
| PRODUCT APPROVALS FOR |
| GARAGE DOOR |
| GLASS BLOCK |
| FIXED GLASS WINDOW |
| |
| 7.)PROVIDE CORRECT PRODUCT APPROVAL |
| AND STATEWIDE PRODUCT APPROVAL FOR THE |
| SHUTTERS.SAFEGUARD IS OUT OF BUSINESS. |
| |
| 8.)REMOVE THE TITLE BLOCK FOR AFFINITI |
| FROM THE PLAN AS THEY ARE NOT THE |
| DESIGNER OF RECORD. |
| |
| 9.)THE ENGINEER'S NAME AND LICENSE |
| NUMBER IS TO BE PRINTED ON THE PLAN, |
| FAC61G15-23.002. |