Date |
Text |
2004-04-15 00:00:00 | DENIED |
| |
| 1)THE ENGINEER'S TITLE BLOCK INFORMATION |
| IS ILLEGIBLE ON SOME SHEETS OF THE |
| PLANS, WHERE STAMPED ON TOP OF OTHER |
| INFORMATION. PLEASE CORRECT. |
| |
| 2) FBC SECTION 2319.17 REFERENCED UNDER |
| WOOD CONSTRUCTION NOTES ON SHEET 7 ONLY |
| APPLIES IN THE HIGH VELOCITY HURRICANE |
| ZONE. THIS DOES NOT APPLY IN THE CITY OF |
| WPB WHICH IS NOT LOCATED IN THE HVHZ. |
| PLEASE REMOVE THIS FROM THE PLAN. |
| |
| 3) THE USP TA16 CONNECTOR REQUIRES (9) |
| 10D NAILS FOR 1205# OF UPLIFT. CORRECT |
| THIS ON THE ANCHOR SCHEDULE ON RF-1. |
| |
| 4) THE TRUSS ANCHOR SCHEDULES ON RF-1 |
| AND SD2 CONTAIN CONFLICTING INFORMATION. |
| THE UPLIFT VALUES ARE DIFFERENT FOR THE |
| SAME ID TAGS. PLEASE REMOVE ONE OF THEM |
| FROM THE PLANS. |
| |
| 5) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVAL FOR THE WEATHERGUARD STORM |
| PANELS. SPECIFY THE CONNECTION TYPE AND |
| FASTENERS THAT WILL BE USED BY CIRCLING |
| OR HIGHLIGHTING THE APPROPRIATE ITEMS ON |
| THE PRODUCT APPROVALS. |
| |
| 6)PLEASE SUBMIT THE FOLLOWING ADDITIONAL |
| INFORMATION REQUIRED FOR THE ROYAL WALL |
| SYSTEM. SUBMIT ENGINEERING CALCULATIONS |
| FOR THE PANELS. SUBMIT A LETTER FROM A |
| LICENSED THRESHOLD INSPECTOR STATING |
| THAT AN INSPECTION WILL BE MADE AT THE |
| MANUFACTURED SITE OF THE JOB SPECIFIC |
| COMPONENTS TO VERIFY CONSTRUCTION |
| COMPLIANCE OF THE COMPONENTS WITH THE |
| ENGINEERED DESIGN. SEE ATTACHED MEMO. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |