Plan Review Notes
Plan Review Notes For Permit 03120124
Permit Number 03120124
Review Stop B
Sequence Number 2
Notes
Date Text
2004-04-15 00:00:00DENIED
  
 1)THE ENGINEER'S TITLE BLOCK INFORMATION
 IS ILLEGIBLE ON SOME SHEETS OF THE
 PLANS, WHERE STAMPED ON TOP OF OTHER
 INFORMATION. PLEASE CORRECT.
  
 2) FBC SECTION 2319.17 REFERENCED UNDER
 WOOD CONSTRUCTION NOTES ON SHEET 7 ONLY
 APPLIES IN THE HIGH VELOCITY HURRICANE
 ZONE. THIS DOES NOT APPLY IN THE CITY OF
 WPB WHICH IS NOT LOCATED IN THE HVHZ.
 PLEASE REMOVE THIS FROM THE PLAN.
  
 3) THE USP TA16 CONNECTOR REQUIRES (9)
 10D NAILS FOR 1205# OF UPLIFT. CORRECT
 THIS ON THE ANCHOR SCHEDULE ON RF-1.
  
 4) THE TRUSS ANCHOR SCHEDULES ON RF-1
 AND SD2 CONTAIN CONFLICTING INFORMATION.
 THE UPLIFT VALUES ARE DIFFERENT FOR THE
 SAME ID TAGS. PLEASE REMOVE ONE OF THEM
 FROM THE PLANS.
  
 5) SUBMIT STATE OR LOCAL PRODUCT
 APPROVAL FOR THE WEATHERGUARD STORM
 PANELS. SPECIFY THE CONNECTION TYPE AND
 FASTENERS THAT WILL BE USED BY CIRCLING
 OR HIGHLIGHTING THE APPROPRIATE ITEMS ON
 THE PRODUCT APPROVALS.
  
 6)PLEASE SUBMIT THE FOLLOWING ADDITIONAL
 INFORMATION REQUIRED FOR THE ROYAL WALL
 SYSTEM. SUBMIT ENGINEERING CALCULATIONS
 FOR THE PANELS. SUBMIT A LETTER FROM A
 LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE
 MANUFACTURED SITE OF THE JOB SPECIFIC
 COMPONENTS TO VERIFY CONSTRUCTION
 COMPLIANCE OF THE COMPONENTS WITH THE
 ENGINEERED DESIGN. SEE ATTACHED MEMO.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714