Plan Review Notes
Plan Review Notes For Permit 03120124
Permit Number 03120124
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00DENIED
  
 1) THE STRUCTURAL PLANS AND THE SURVEY
 ARE REVERSED. PLEASE REVISE.
  
 2) THE NOTE ON SHEET 2 REFERS TO THE
 1997 STANDARD GAS CODE. PLEASE UPDATE TO
 2001 FBC FUEL GAS CODE.
  
 3) WINDOWS WITH THE BOTTOM EDGE WITHIN
 18" OF THE FLOOR AND INDIVIDUAL PANE
 SIZE OF AT LEAST 9 SQUARE FEET ARE
 REQUIRED TO BE SAFETY GLASS PER FBC
 2405.2.1 (4). LIVING ROOM AND DINING
 ROOM WINDOWS APPEAR TO FALL UNDER THIS
 REQUIREMENT. SPECIFY ON THE PLANS.
  
 4)A MEAN ROOF HEIGHT OF 25'-35' REQUIRES
 THE ROOF SHEATHING TO BE NAILED WITH 8D
 RING SHANKED NAILS IN ZONE 3 PER CITY
 AMENDMENTS TO FBC TABLE 2306.1. REVISE
 ROOF SHEATHING NAILING NOTE ON SHEET 4.
  
 5) UPDATE THE REFERENCES TO HUGHES
 CONNECTORS ON SHEET 3. HUGHES WAS
 PURCHASED BY USP. REFERENCE CONNECTORS
 FROM A CURRENT MANUFACTURER WITH STATE
 OF FLORIDA PRODUCT APPROVAL.
  
 6) LIST THE ENGINEER'S FIRM LICENSE
 NUMBER IN THE TITLE BLOCK ON ALL SHEETS
 SIGNED AND SEALED BY HIM. THE NUMBER
 THAT IS ON 2 OF THE SHEETS DOES NOT
 MATCH THE LICENSE # FOR PERMIT ENGINEER-
 ING SERVICES LISTED BY THE FBPE. PLEASE
 CORRECT.
  
 7) THE WOOD CONSTRUCTION NOTES ON SHEET7
 SITES FBC 3218.17. THERE IS NO SUCH CODE
 SECTION IN THE 2001 FBC. PLEASE CORRECT.
  
 8) THE USP TA16 CONNECTOR RTEQUIRES (9)
 10D NAILS PER 2003 USP CATALOG. PLEASE
 REVISE THE ANCHOR SCHEDULE ON RF-1.
  
 9) CLARIFY THE NOTE IN THE CENTER OF
 SHEET 1 OF THE ROYAL WALL SYSTEM PLANS
 FOR THE 10'-2" WALLS.
  
 10) TWO CONFLICTING UPLIFT ANCHOR
 SCHEDULES ARE GIVEN ON RF-1 AND SD2.
 PLEASE CORRECT.
  
 11) PROVIDE STATE OF FLORIDA PRODUCT
 APPROVAL OR SITE SPECIFIC LOCAL PRODUCT
 APPROVAL AS REQUIRED BY STATE LAW (SEE
 WWW.FLORIDABUILDING.ORG. AND RULE 9B-72,
 F.A.C.) FOR THE ROYAL WALL SYSTEM,
 SLIDING GLASS DOORS, SINGLE HUNG WINDOWS
 ENTRY DOOR, GARAGE DOOR, FIXED WINDOWS,
 MULLIONS, GLASS BLOCK, ROOF TILE AND
 TRUSS ANCHORS.
  
 12) SAFEGUARD IS NO LONGER IN BUSINESS.
 SUBMIT STATE PRODUCT APPROVAL FOR STORM
 PANELS, KEY PLAN AND INSTALLATION
 SCHEDULE. REVISE KEY PLAN AND SCHEDULE
 TO INDICATE IMPACT GLASS AT DEN WINDOW
 FOR EGRESS WHICH WILL NOT BE SHUTTERED.
 NOTE: DOORS TO DEN MUST NOT BE LOCKABLE.
  
 13) AFFINITI TITLE BLOCK SHOULD BE
 REMOVED FROM PLAN. THEY ARE NOT THE
 DESIGNER OF RECORD.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714