Plan Review Notes
Plan Review Notes For Permit 03111252
Permit Number 03111252
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-10 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 3) NEED GRILL SIZES ON PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved