Plan Review Notes For Permit 03111252 |
Permit Number |
03111252 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-09 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE SEE PLANS, RISER SHOWS | | METER CAN FEEDING PANEL, HOWEVER PANEL | | IS SHOWN AS MLO? PLEASE CLARIFY WHERE | | MAIN IS? | | | | 2)NOTE: PLEASE SUBMIT AIC RATING FOR | | MAIN. PANEL IS NOTED FOR BRANCH BRKRS. | | PER 110.9/ 215.5 | | | | 3)NOTE: PLEASE LIST THE REQ'D DEDICATED | | BATH CIRCUIT PER 210.11C3/210.52D. MUST | | BE 20A AND #12. | | | | 4)NOTE: PLEASE SEE THAT PLANS MUST | | CONTAIN A COMPLETE SIGNATURE PER FS | | 481.221 AND FAC 61G1-16.004 | | THIS OFFICE HAS BEEN NOTIFIED BY THE | | STATE BOARD, A "SIGNATURE" SHOULD | | CONTAIN A MIN OF FIRST AND LAST NAME | | AND INITIALS ARE NOT ACCEPTABLE. | | | | 5)NOTE: PLEASE SHOW RECEPT FOR ISLAND AS | | GFI/GFI PROTECTED. 210.8A6 | | | | 6)NOTE: PLEASE SEE THAT PANEL IS NOT | | PERMITTED IN WHAT APPEARS TO BE A | | STORAGE CLOSET. 384.7, 110.26 ETC. | | PLANS MUST SHOW THIS ROOM AS A DEDICATED | | MECH/ELEC RM. NO STORAGE PERMITTED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|