 THE REVISION SUBMITED REFERS TO A "60
 AMP SUB PANEL FOR THE SECOND FLOOR",BUT
 THE ADDED 60 AMP PANEL ON THE PLAN HAS
 POOL CIRCUITS ON ITS SCHEDULE.
  
 THERE ARE FOUR ITEMS ON THE LIST
 SUBMITTED WITH THIS REVISION THAT REFER
 TO ITEMS ON THE SECOND FLOOR, BUT NO
 SECOND FLOOR DRAWING WAS SUBMITTED FOR
 REVIEW.
  
 PLEASE CLARIFY THESE ITEMS AND REMOVE
 COMMENTS OR ADD SHEETS AS NECESSARY.
  