Date |
Text |
2003-12-17 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4) SAFETY GLAZING IS REQUIRED WITHIN |
| 3' HORIZONTALLY OF A TUB OR SHOWER PER |
| FBC 2405.2. SPECIFY ON THE PLANS THAT |
| WINDOW (U) BESIDE THE TUB IN THE SECOND |
| FLOOR BATH #2 IS TEMPERED. |
| |
| 5) SPECIFY THE FASTENERS (LENGTH/EMBED) |
| FOR ATTACHING THE TRUSS BUCKETS TO THE |
| WALL. SEE SHEET A7. |
| |
| 6) INDICATE ON THE COLUMN BASE DETAILS |
| ON A7 TO REFER TO THE DETAIL ON A13 FOR |
| ANCHORING DETAIL. |
| |
| 7) FBC 1015.3 REQUIRES THE BOTTOM RAIL |
| ON A GUARDRAIL TO REJECT A 2" SPHERE. |
| PLEASE CORRECT THE RAILING DETAIL ON A12 |
| |
| 8) THE WALL SECTIONS ON A12 SPECIFY A |
| ATTIC INSULATION WITH A MINIMUM OF R-30 |
| AND THE ENERGY CALCS. LISTS R-19. |
| PLEASE CORRECT. |
| |
| 9) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL PER FAC |
| RULE 9B-72. SEE FORM ATTACHED. |
| |
| 10) THE DESIGN PRESSURES ON THE PRODUCT |
| APPROVAL FOR THE OVERHEAD GARAGE DOOR |
| DOES NOT MEET THE PRESSURES LISTED ON |
| THE PLANS. |
| |
| 11) THE PRODUCT APPROVAL SUBMITTED FOR |
| THE GLAZED EXTERIOR DOOR IS FOR A DOOR |
| WITH SIDELITES, THE DOOR ON THE PLANS |
| DOES NOT HAVE SIDELITES. SUBMIT THE |
| APPROPRIATE PRODUCT APPROVAL. NOTE THE |
| ONE SUBMITTED DOES NOT MEET THE REQUIRED |
| PRESSURES LISTED IN THE SCHEDULE ON A1. |
| |
| 12) THE KEY PLAN AND SCHEDULE SUBMITTED |
| FOR THE STORM PANELS DOES NOT MATCH THE |
| PLANS (SECOND FLOOR). SUBMIT REVISED |
| KEY AND SCHEDULE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |