Plan Review Notes
Plan Review Notes For Permit 03111080
Permit Number 03111080
Review Stop E
Sequence Number 7
Notes
Date Text
2005-08-10 00:00:00****** REVISION UNSAT *********
  
  
 1)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE NOTICE THERE ARE MORE THAN 75
 RECESSED LT FIXTURES.
  
 2)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH THE REVISED SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE DINING RM CIRCUIT NOT ON
 PLANS? ETC.
 215.5
  
 3)NOTE: PLEASE SEE 210.52B1, WHICH
 REQUIRES DINING RM TO BE ON THE ONE OR
 MORE 20, #12, SMALL APPLIANCE CIRCUITS.
 PLEASE SEE DINING RM CIRCUIT ON PANEL
 SCHEDULE IS SHOWN AS #14 AWG AND 15A?
  
 4)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS TO PLANS.
 215.5
  
 5)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE REQUIRED FOR RECESSED LTS IN
 CLOSETS. PLEASE SEE SOME APPEAR TO BE
 LOCATED TOO CLOSE TO POSSIBLE SHLEVING
 AREAS. THIS IS ONLY A NOTE AS NO
 SHELVING IS SHOWN. PLEASE SEE A MIN OF
 18" IS TO BE PROVIDED FOR SHELVING AND
 THEN MIN CLEARENCE IS REQUIRED AFTER THE
 18". PLEASE VERIFY THESE MIN AREAS.
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPT
 ALONG KITCHEN COUNTERSPACE. 210.52C1
  
 7)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52, WITH IN 6' OF DOOR WAY? DINING
 AREA? BEDRM?
  
 8)NOTE: PLEASE SEE GEN LT/RECEPT CIRCUIT
 SHOWN WITH A #10 EQUIPMENT GROUNDING
 CONDUCTOR?? MISPRINT?
 250.122
  
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINEDS ON PLANS AT LOCATION SOF
 THE ABOVE COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL THIS
 OFFICE.
  