2005-08-10 00:00:00 | ****** REVISION UNSAT ********* |
| |
| |
| 1)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| PLEASE NOTICE THERE ARE MORE THAN 75 |
| RECESSED LT FIXTURES. |
| |
| 2)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| ON PLANS WITH THE REVISED SUBMITTED |
| PANEL SCHEDULE. |
| PLEASE SEE DINING RM CIRCUIT NOT ON |
| PLANS? ETC. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE 210.52B1, WHICH |
| REQUIRES DINING RM TO BE ON THE ONE OR |
| MORE 20, #12, SMALL APPLIANCE CIRCUITS. |
| PLEASE SEE DINING RM CIRCUIT ON PANEL |
| SCHEDULE IS SHOWN AS #14 AWG AND 15A? |
| |
| 4)NOTE: PLEASE SHOW ALL ROOM/AREA |
| DESIGNATIONS TO PLANS. |
| 215.5 |
| |
| 5)NOTE: PLEASE SEE 410.8 FOR MIN |
| CLEARENCE REQUIRED FOR RECESSED LTS IN |
| CLOSETS. PLEASE SEE SOME APPEAR TO BE |
| LOCATED TOO CLOSE TO POSSIBLE SHLEVING |
| AREAS. THIS IS ONLY A NOTE AS NO |
| SHELVING IS SHOWN. PLEASE SEE A MIN OF |
| 18" IS TO BE PROVIDED FOR SHELVING AND |
| THEN MIN CLEARENCE IS REQUIRED AFTER THE |
| 18". PLEASE VERIFY THESE MIN AREAS. |
| |
| 6)NOTE: PLEASE SEE MISSING GFI RECEPT |
| ALONG KITCHEN COUNTERSPACE. 210.52C1 |
| |
| 7)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52, WITH IN 6' OF DOOR WAY? DINING |
| AREA? BEDRM? |
| |
| 8)NOTE: PLEASE SEE GEN LT/RECEPT CIRCUIT |
| SHOWN WITH A #10 EQUIPMENT GROUNDING |
| CONDUCTOR?? MISPRINT? |
| 250.122 |
| |
| |
| PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| BEEN REDLINEDS ON PLANS AT LOCATION SOF |
| THE ABOVE COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL THIS |
| OFFICE. |
| |