Plan Review Notes
Plan Review Notes For Permit 03111080
Permit Number 03111080
Review Stop E
Sequence Number 5
Notes
Date Text
2004-07-06 00:00:00************ UNSAT 5TH TIME *********
  
 1)NOTE: PLEASE SEE 2002 NEC 210.12
 PLEASE LIST THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS.
 THIS IS REQUIRED FOR ALL "OUTLETS" IN
 BEDROOMS, INCLUDING SD'S, LTS, RECEPTS,
 FANS.
 THIS HAS BEEN REQUESTED ON THE PREVIOUS
 FOUR REVIEWS.
  
 2)NOTE: PLEASE SEE THERE ARE A FEW
 RECEPTS WITH CIRCUIT #'S MISSING.
 PLEASE SEE # OF RECEPTS ON CIRCUIT #5
 180 VA PER RECEPT.?
  
  
 ** PLEASE SEE ATTACHED BZ RECEIPT,
 A 4X FEE HAS NOW BEEN ACCESSED FOR PLAN
 REVIEW COMMENTS AS SET FORTH FOR BLDG
 AND ELECTRICAL COMMENTS.
 A NOTICE WAS GIVEN ON PREVIOUS REVIEWS,
 PER FS 553.80(2)(B).
 THIS FEE IF $1,218.00 IS REQUIRED TO BE
 PAID BEFORE RESUBMITTING PLANS.
 ONCE MORE, ONE SET OF PLANS ARE BEING
 RETAINED AND MAY BE SENT TO FBPE'S FOR
 REVIEW OF CODE COMPLIANCE ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 AS TO DATE NO PHONE CALLS HAVE BEEN
 RECIEVED FROM DESIGN PROFESSIONAL TO GO
 OVER COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]