2004-06-10 00:00:00 | ************ UNSAT 4TH TIME *********** |
| |
| PLEASE SEE NOTES FROM PREVIOUS REVIEWS. |
| PLEASE SEE ONLY TWO OF THE PREVIOUS |
| 6 NOTES WERE ADDRESSED. |
| |
| 1)NOTE: |
| NOTE #1OK. TURQUOISE ENG NAME WAS |
| REMOVED. |
| |
| 2)NOTE: |
| NOTE #2 NO. PLEASE SHOW "ALL" CIRCUITING |
| ON PLANS AND CORRELATE WITH THE SUBMITT- |
| -ED PANEL SCHEDULE. PLEASE SEE 2002 NEC |
| FOR ALL MIN CIRCUITS REQUIRED IN A |
| DWELLING UNIT. WASHER? DRYER? 215.5, |
| 220.16,220.18, |
| |
| 3)NOTE: |
| NOTE #3OK |
| |
| 4)NOTE: |
| NOTE #4NO, SOME RECEPTS STILL MISSING |
| FOR 2' OF WALL SPACE. |
| |
| 5)NOTE: |
| NOTE #5 NO, PLEASE LIST THE REQUIRED |
| ARC FAULT PROTECTED CIRCUITS PER 2002 |
| NEC 210.12 |
| PLEASE SEE 2002 NEC REQUIRES THIS FOR |
| LTS/SD'S RECEPTS/FANS ETC. ALL "OUTLETS" |
| IN SLEEPING RMS. |
| |
| 6)NOTE: |
| NOTE #6NO, PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| PLEASE SEE ONE OF THESE SETS ARE NOW |
| BEING RETAINED ALSO DUE TO REPEAT |
| COMMENTS. |
| PLEASE ALSO SEE ATTACHED COPY OFTHE |
| FS 553.80(2)(B). IF ANY OF THE COMMENTS |
| FOR CODE COMPLIANCE ARE NOT ADDRESSED |
| ON NEXT REVIEW A 4X FEE WILL BE ACCESSED |
| TO THE DESIGN PROFESSIONAL. |
| ****PLEASE SEE ATTACHED COPY***** |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| ONCE AGAIN, PLEASE DO NOT HESITATE TO |
| CALL. AS OF THIS REVIEW, DESIGNER OF |
| RECORD HAS NOT CONTACTED ELECTRICAL |
| PLAN REVIEW STAFF FOR ANY QUESTIONS. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |