Plan Review Notes
Plan Review Notes For Permit 03111080
Permit Number 03111080
Review Stop E
Sequence Number 4
Notes
Date Text
2004-06-10 00:00:00************ UNSAT 4TH TIME ***********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
 PLEASE SEE ONLY TWO OF THE PREVIOUS
 6 NOTES WERE ADDRESSED.
  
 1)NOTE:
 NOTE #1OK. TURQUOISE ENG NAME WAS
 REMOVED.
  
 2)NOTE:
 NOTE #2 NO. PLEASE SHOW "ALL" CIRCUITING
 ON PLANS AND CORRELATE WITH THE SUBMITT-
 -ED PANEL SCHEDULE. PLEASE SEE 2002 NEC
 FOR ALL MIN CIRCUITS REQUIRED IN A
 DWELLING UNIT. WASHER? DRYER? 215.5,
 220.16,220.18,
  
 3)NOTE:
 NOTE #3OK
  
 4)NOTE:
 NOTE #4NO, SOME RECEPTS STILL MISSING
 FOR 2' OF WALL SPACE.
  
 5)NOTE:
 NOTE #5 NO, PLEASE LIST THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS PER 2002
 NEC 210.12
 PLEASE SEE 2002 NEC REQUIRES THIS FOR
 LTS/SD'S RECEPTS/FANS ETC. ALL "OUTLETS"
 IN SLEEPING RMS.
  
 6)NOTE:
 NOTE #6NO, PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SEE ONE OF THESE SETS ARE NOW
 BEING RETAINED ALSO DUE TO REPEAT
 COMMENTS.
 PLEASE ALSO SEE ATTACHED COPY OFTHE
 FS 553.80(2)(B). IF ANY OF THE COMMENTS
 FOR CODE COMPLIANCE ARE NOT ADDRESSED
 ON NEXT REVIEW A 4X FEE WILL BE ACCESSED
 TO THE DESIGN PROFESSIONAL.
 ****PLEASE SEE ATTACHED COPY*****
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 ONCE AGAIN, PLEASE DO NOT HESITATE TO
 CALL. AS OF THIS REVIEW, DESIGNER OF
 RECORD HAS NOT CONTACTED ELECTRICAL
 PLAN REVIEW STAFF FOR ANY QUESTIONS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]