Plan Review Notes
Plan Review Notes For Permit 03111080
Permit Number 03111080
Review Stop E
Sequence Number 3
Notes
Date Text
2004-05-08 00:00:00******** UNSAT **********
  
 PLEASE SEE NOTES FROM FIRST TWO
 REVIEWS HAVE STILL NOT BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING.
  
 1)NOTE: PLANS MUST CONTAIN ALL LICENSE
 #'S ON TITLE BLOCK AS REQ'D UNDER FAC
 61G15-23.002. PLEASE SEE FS 471.023
 TURQUOIUSE INC. MUST HAVE A CA#.
 THERE IS NO CA# FOUND WITH DBPR/ FBPE'S
 THIS COMMENT HAS BEEN MADE ON PREVIOUS
 REVIEWS ON THIS PROJECT AND OTHER
 PROJECTS SUBMITTED TO THE CITY OF WPB
 FOR PERMIT.
 PLEASE ALSO SEE FS 471.025, DATE MUST
 ALSO BE SIGNED ON PLANS WHEN ENGINEER
 SIGNS HIS/HER SIGNATURE.
 WE ARE NOW RETAINING ONE SET OF PLANS
 TO BE TURNED OVER TO FBPE'S FOR REVIEW
 FOR ABOVE MENTIONED.
  
 2)NOTE: PLANS MUST SHOW ALL MIN CIRCUIT-
 -ING AS SET FORTH PER 2002 NEC.
 PLEASE SHOW CIRCUITS ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE. MISSING SOME.
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]