Plan Review Notes
Plan Review Notes For Permit 03111080
Permit Number 03111080
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-23 00:00:00DENIED:
 NO MECHANICAL PLANS OR FORM 600C
 SUBMITTED FOR REVIEW.PER 2001 FBC
 CHAPTER 13 SUB-CHAPTER 600 METHOD C,
 RENOVATIONS TO EXISTING RESIDENCE ARE
 TO COMPLY WITH THIS METHOD.
  
 PLANS NEED TO INCLUDE DUCT/GRILLE SIZE,
 LAYOUT AND MATERIAL.RETURN OR TRANSFER
 AIR REQUIRED FROM BEDROOM AREAS PER 2001
 FBC(M) 601.4 (SEE ATTACHED FOR SIZING
 REQUIREMENTS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.