2003-12-24 00:00:00 | 1) MORE DETAILS REQUIRED ON SMOKE | | DETECTORS. ALL NEW SMOKE DETECTORS | | SHALL BE ELECTRIC. THESE DEVICES SHALL | | BE INSTALLED A MINIMUM OF THREE FEET | | FROM AIR CONDITIONER DIFFUSERS. S.D. | | NOT ON LABEL. | | | | 2) ENTRY DOOR IS REQUIRED TO BE FIRE | | RATED.NO INFORMATION PROVIDED ABOUT | | RATING. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|