1 |
|
Notes |
Date |
Text |
2003-11-24 00:00:00 | 1) BEDROOMS NEED TO BE ON ARC FAULT | | CIRCUIT BREAKERS | | 2)SWITCH BY SLIDING DOOR NEAR KITCHEN | | HAS NO LOAD. | | 3) SWITCH LEG FOR LIVING ROOM LIGHTS | | LOOK INCOMPLETE. ALSO THERE IS THREE | | FIXTURES THAT HAVE NO SWITCH LEG SHOWN. | | 4) DISCONNECTS REQUIRED FOR THE | | WATERHRT & A/C | | 5) CLOSET FOR WATER HEATER AND A/C | | NEEDS LIGHT AND RECEPTACLE FOR | | SERVICING. | | 6) NO TVS OR TELE. SHOWN ON DRAWINGS IF | | NOT SHOWN A SEPERATE PERMIT WILL BE | | REQUIRED FOR BOTH. | | 7) NO CIRCUITS SHOWN ON DRAWINGS. | | 8) NO CIRCUITS SHOWN FOR SMOKE | | DETECTORS9) OUTLET SPACING BY KITCHEN | | IN LIVING | | ROOM IS NOT TO CODE. |
|