Plan Review Notes
Plan Review Notes For Permit 03111034
Permit Number 03111034
Review Stop P
Sequence Number 3
Notes
Date Text
2004-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEWS: SUBMIT CALCU-
 LATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 2) SHOW LOCATION OF ALL PRIMARY ROOF
 DRAINS. 104.2.1
 3) THE NEW PLANS HAVE NOT BEEN SUBMITTED
 AT THIS TIME. ONLY TWO SETS OF OLD
 SHEETS HAVE BEEN SUBMITTED. SUBMIT TWO
 SETS OF PLANS FOR REVIEW. SHEET 2 IS
 MISSING FROM BOTH OLD SETS OF PLANS.
 104.2.1
 4) SCUPPER DETAIL REQUIRED. 104.2.1
 5) A STORM RISER DIAGRAM IS REQUIRED IN
 ISOMETRIC FORM WITH ALL PIPE SIZES AND
 SHOW TERMINATION POINT. 104.3.1.1
 6) THE PERSON SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 ********THE DATE IS STILL MISSING*******
 FAC G161-16.003 & FS 481.2055.
 7) 4 TIMES THE FEE REQUIRED FOR PLAN RE-
 VIEW IS NOW BEING IMPOSED PER FS 533.80
 (2)(B). THE FEE WILL BE PAID AT THE TIME
 THE PLANS WILL BE PICKED UP. ($720.00)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]