Plan Review Notes For Permit 03111034 |
Permit Number |
03111034 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-12 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 BUILDING | | FLA. ADMIN. CODE | | FLA. STATUTES | | | | 1) FROM PREVIOUS REVIEW: RESPONSE NOTED: | | SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS. SHOW SQUARE FOOT- | | AGE OF ROOF AREA. SHOW 1/2 AREA OF ALL | | VERTICAL WALLS INCLUDING PARAPETS. SEE | | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS | | PRIMARY ROOF DRAINS SHALL BE INSTALLED | | IN THE "SHELL" PHASE OF THE BLDG. | | 2) SCUPPER DETAIL DOES NOT SHOW THE | | WIDTH OF THE SCUPPERS. | | 3) SUBMIT A STORM RISER DIAGRAM SHOWING | | ALL PIPE SIZES AND TERMINATION POINT. | | 4) SHOW LOCATION OF ALL PRIMARY DRAINS. | | 5) THE PERSONAL SEAL, SIGNATURE, AND | | DATE OF THE ARCHITECT SHALL APPEAR ON | | ALL DOCUMENTS TO BE FILED FOR PUBLIC | | RECORD. ***THE DATE IS STILL MISSING*** | | 61G1-16.003 & FS481.2055 | | 5) THE LICENSE NUMBER IS REQUIRED ON THE | | TITLE BLOCK ON EACH SHEET. 61G1-16.004 | | FS481.2055 | | 6) SEE ATTATCHED SHT. CONCERNING FLORIDA | | STATUTE 533.80(2)(B). | | 7) SUBMIT TWO COMPLETS SETS OF PLANS FOR | | REVIEW AND STAMPING. TWO OLD SETS AND | | ONE NEW SET WERE SUBMITTED THIS REVIEW. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|