Plan Review Notes
Plan Review Notes For Permit 03111034
Permit Number 03111034
Review Stop P
Sequence Number 2
Notes
Date Text
2004-01-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) FROM PREVIOUS REVIEW: RESPONSE NOTED:
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW SQUARE FOOT-
 AGE OF ROOF AREA. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS. SEE
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 PRIMARY ROOF DRAINS SHALL BE INSTALLED
 IN THE "SHELL" PHASE OF THE BLDG.
 2) SCUPPER DETAIL DOES NOT SHOW THE
 WIDTH OF THE SCUPPERS.
 3) SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES AND TERMINATION POINT.
 4) SHOW LOCATION OF ALL PRIMARY DRAINS.
 5) THE PERSONAL SEAL, SIGNATURE, AND
 DATE OF THE ARCHITECT SHALL APPEAR ON
 ALL DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD. ***THE DATE IS STILL MISSING***
 61G1-16.003 & FS481.2055
 5) THE LICENSE NUMBER IS REQUIRED ON THE
 TITLE BLOCK ON EACH SHEET. 61G1-16.004
 FS481.2055
 6) SEE ATTATCHED SHT. CONCERNING FLORIDA
 STATUTE 533.80(2)(B).
 7) SUBMIT TWO COMPLETS SETS OF PLANS FOR
 REVIEW AND STAMPING. TWO OLD SETS AND
 ONE NEW SET WERE SUBMITTED THIS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]