2004-01-21 00:00:00 | *****CORRECTIONS****** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEE PREVIOUS LIST, ITEM #1.NOT |
| ADDRESSED.SUBMIT A COPY OF A SURVEY |
| FOR THIS PROPERTY, ADDRESSING TABLE 600 |
| ISSUES.SHOW THE DISTANCE BETWEEN THE |
| TWO BUILDINGS ON THIS PROPERTY, DISTANCE |
| TO THE PROPERTY LINE.SHOW THE |
| ASSUMED PROPERTY LINE, WITH DIMENSIONS, |
| AND SUBMIT CALCULATIONS SHOWING TABLE |
| 600 COMPLIANCE.FAILURE TO PROVIDE THE |
| REQUESTED INFORMATION MAY RESULT IN |
| ADDITIONAL PERMITTING DELAYS. |
| |
| 2.)SEE PREVIOUS LIST, ITEM #3, NOT |
| ADDRESSED. |
| |
| 3.)THE PLANS MAKE REFERENCE "TO CODE". |
| THIS IS NOT AN ACCEPTABLE AS A DETAIL, |
| FBC104.2.1.ALL MATERIALS, DIMENSIONS, |
| ETC. MUST BE SPECIFIED. |
| |
| 4.)SEE PREVIOUS LIST, ITEM #5, |
| REGARDING FBC3401.7.2.6.SOME COMMENTS |
| ARE RELATED TO THIS CODE SECTION |
| (ALTERATIONS OVER 50%). |
| |
| 5.)THE STAIRS DO NOT COMPLY WITH FBC |
| 1007.3. |
| |
| 6.)SEE PREVIOUS LIST, ITEM #9.CANNOT |
| SPECIFY "TO CODE".ALL GUARDRAIL AND |
| HANDRAILS DETAILS ARE TO COMPLY WITH |
| FBC1608, FBC1007.5, FBC1015.THE |
| DETAILS SHOWN ARE NOT CODE COMPLIANT IN |
| DESIGN, INCLUDING HEIGHT, MAKE NO |
| REFERENCE TO STRUCTURAL DESIGN LOAD. |
| THIS ALSO APPLIES TO PREVIOUS LIST #10, |
| EITHER NOT ADDRESSED OR ADDRESSED IN A |
| MANNER WHICH IS NOT CODE COMPLIANT. |
| |
| 7.)CHANGES MADE TO THE PLAN IN INK |
| ARE TO BE INITIALED BY THE ARCHITECT. |
| |
| 8.)SEE PREVIOUS LIST, ITEM #35. MANY |
| CHANGES WERE DONE TO THE PLAN AND NOT |
| INDICATED IN ANY MANNER. |
| |
| 9.)ADDITIONAL FEES DUE, $2163.60, |
| BZ235307.PLEASE RETURN THE BZ GIVEN |
| AT THE LAST REVIEW. |
| |
| 10.)SEE PREVIOUS LIST, ITEM #12.NOT |
| ADDRESSED.TO MY KNOWLEDGE THE PRODUCT |
| APPROVALS SUBMITTED FOR DOORS AND |
| WINDOWS DO NOT HAVE ANY FIRE RATING. |
| |
| 11.)SEE PREVIOUS LIST, ITEM #13, |
| INDICATE CONSTRUCTION TYPE ON THE PLAN. |
| |
| 12.)SHEET 4, LSAT 2", MUST SPECIFY A |
| MODEL #, NOT A DIMENSION.LSTA IS A |
| WOOD-TO-WOOD CONNECTOR WHICH YOU ARE |
| USING IN A WOOD-TO-MASONRY APPLICATION. |
| EITHER SUBMIT DOCUMENTATION FROM THE |
| MANUFACTURER SHOWING THAT THIS |
| APPLICATION IS ACCEPTABLE, SPECIFY A |
| DIFFERENT CONNECTOR, OR SUBMIT SEALED |
| CALCULATIONS FOR THIS CONNECTOR IN THIS |
| APPLICATION.CHECK ALL CONNECTORS. |
| |
| 13.)THE WINDOW/DOOR BUCK DETAIL |
| SPECIFIES "CASE HARDENEND NAILS",SPECIFY |
| SIZE.THE FASTENERS FOR THE WINDOW |
| CONFLICT WITH THE PRODUCT APPROVAL IN |
| BOTH DIAMETER AND SPACING, SEE ATTACHED |
| HIGHLIGHTED PRODUCT APPROVAL. |
| |
| 14.)NOTE THAT THE TEMPERED WINDOWS |
| SHOWN ON THE 2ND FLOOR ARE ALSO REQUIRED |
| TO HAVE A FIRE RESISTANCE RATING, FBC |
| 1006.2.4.DOCUMENTATION SUBMITTED FOR |
| THIS WINDOW IS TO SHOW COMPLIANCE WITH |
| CHAPTER 16, FBC2405.2, AND FBC1006.2.4. |
| |
| 15.)THE GUARDRAIL IS TO BE A MINIMUM |
| OF 44", FBC1015.2.THE DETAILS SHOW |
| THE STAIRRAIL (WHICH SERVES AS A |
| GUARDRAIL) AT 30" AND 36". |
| |
| 16.)HANDRAIL REQUIRED FOR STAIR ON |
| BOTH SIDES, FBC1007.5. |
| |
| 17.)SEE PREVIOUS LIST, ITEM #22, |
| NOT ADDRESSED. |
| |
| 18.)SEE PREVIOUS LIST, ITEM #24. |
| ENERGY CALCS REQUIRED. |
| |
| 19.)SEE PREVIOUS LIST, ITEM #25. |
| RATHER THAN ADDRESS THE COMMENT THE |
| INSULATION WAS REMOVED.INSULATION IS |
| REQUIRED FOR THE FLOOR (OCCUPANCY |
| SEPARATION) AND ROOF. |
| |
| 20.)SEE PREVIOUS LIST, ITEM #29.NOT |
| ADDRESSED.IF THE REQUIRED INFORMATION |
| IS NOT SUBMITTED PRIOR TO PERMIT |
| ISSUANCE, A SEPARATE PERMIT FOR SHUTTERS |
| WILL BE REQUIRED. |
| |
| 21.)SEE PREVIOUS LIST, ITEM #26.ALSO |
| HAVE THE NEW PLANS APPROVED BY HISTORIC |
| PRIOR TO RESUBMITTAL. |
| |
| 22.)SPECIFY THE SPACING AND LENGTH OF |
| THE ANCHOR BOLT, SHEET 4, WALL SECTION |
| AT BALCONY. |
| |
| 23.)SEPARATE PERMITS REQUIRED. |
| |
| 24.)SEE PREVIOUS LIST, ITEM #37.NOT |
| ADDRESSED. |
| |
| 25.)RESOLVE ANY EXPIRED PERMIT ISSUES |
| PRIOR TO ISSUANCE OF THIS PERMIT. |
| |
| 26.)AS DISCUSSED SEVERAL TIMES WITH |
| THE CONTRACTOR, IF YOU WISH TO OBTAIN A |
| PERMIT FOR THE ROOF JOISTS, SHEATHING, |
| AND ROOF COVERING ONLY, SUBMIT A PERMIT |
| APPLICATION WITH PLANS SHOWING ONLY |
| THESE ITEMS.PLANS ARE REQUIRED SHOWING |
| DRAINAGE, DESIGN LOAD AND UPLIFT. |
| |
| 27.)SLIDING GLASS DOOR PRODUCT |
| APPROVALS WERE SUBMITTED, NONE SHOWN ON |
| THE PLAN. |
| |
| 28.)MULLION PRODUCT APPROVALS |
| REQUIRED, SUBMIT 2 COPIES. |
| |
| 29.)SHEET 2 IS NOW MISSING FROM THE |
| OLD SETS OF PLANS.ALWAYS SUBMIT ALL |
| OLD SHEETS WITH RESUBMITTAL.THE NEW |
| SHEET 2 NOW SHOWS WINDOWS AS EXISTING. |
| MY UNDERSTANDING IS THAT THIS BUILDING |
| DOES NOT HAVE WINDOWS AND THAT THIS WORK |
| IS TO BE INCLUDED IN THIS PERMIT. |
| REVISE. |
| |
| 30.)SEE ATTACHED NOTICE IN REGARDS TO |
| FS553.80(2)(B). |
| |
| 31.)PAY FEES PRIOR TO RESUBMITTAL. |
| |
| 32.)TWO COPIES OF ALL DOCUMENTATION |
| REQUIRED FOR PERMITTING, ONLY ONE SET |
| OF PLANS WERE SUBMITTED. |
| |
| 33.)SEE PREVIOUS LIST, ITEM #6.THE |
| FIRST FLOOR SHOULD BE DECLARED AS |
| MERCANTILE, 2ND FLOOR AS R2 FBC CH.3. |
| |
| 34.)SEE PREVIOUS LIST, ITEM #37.IN |
| ADDITION TO PROVIDING THE REQUESTED |
| INFORMATION FOR THE OCCUPANCY SEPARATION |
| ALSO PROVIDE SAME FOR TENANT SEPARATION |
| ON THE 1ST FLOOR, FBC704.3.1. |
| |
| 35.)"EXISTING PLUMBING PIPE" IS SHOWN |
| ON THE PLAN (SHEET2, 2ND FLOOR). |
| PENETRATIONS ARE TO COMPLY WITH FBC705.2 |
| .1.3, 705.4. |