Plan Review Notes
Plan Review Notes For Permit 03111034
Permit Number 03111034
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-21 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1.NOT
 ADDRESSED.SUBMIT A COPY OF A SURVEY
 FOR THIS PROPERTY, ADDRESSING TABLE 600
 ISSUES.SHOW THE DISTANCE BETWEEN THE
 TWO BUILDINGS ON THIS PROPERTY, DISTANCE
 TO THE PROPERTY LINE.SHOW THE
 ASSUMED PROPERTY LINE, WITH DIMENSIONS,
 AND SUBMIT CALCULATIONS SHOWING TABLE
 600 COMPLIANCE.FAILURE TO PROVIDE THE
 REQUESTED INFORMATION MAY RESULT IN
 ADDITIONAL PERMITTING DELAYS.
  
 2.)SEE PREVIOUS LIST, ITEM #3, NOT
 ADDRESSED.
  
 3.)THE PLANS MAKE REFERENCE "TO CODE".
 THIS IS NOT AN ACCEPTABLE AS A DETAIL,
 FBC104.2.1.ALL MATERIALS, DIMENSIONS,
 ETC. MUST BE SPECIFIED.
  
 4.)SEE PREVIOUS LIST, ITEM #5,
 REGARDING FBC3401.7.2.6.SOME COMMENTS
 ARE RELATED TO THIS CODE SECTION
 (ALTERATIONS OVER 50%).
  
 5.)THE STAIRS DO NOT COMPLY WITH FBC
 1007.3.
  
 6.)SEE PREVIOUS LIST, ITEM #9.CANNOT
 SPECIFY "TO CODE".ALL GUARDRAIL AND
 HANDRAILS DETAILS ARE TO COMPLY WITH
 FBC1608, FBC1007.5, FBC1015.THE
 DETAILS SHOWN ARE NOT CODE COMPLIANT IN
 DESIGN, INCLUDING HEIGHT, MAKE NO
 REFERENCE TO STRUCTURAL DESIGN LOAD.
 THIS ALSO APPLIES TO PREVIOUS LIST #10,
 EITHER NOT ADDRESSED OR ADDRESSED IN A
 MANNER WHICH IS NOT CODE COMPLIANT.
  
 7.)CHANGES MADE TO THE PLAN IN INK
 ARE TO BE INITIALED BY THE ARCHITECT.
  
 8.)SEE PREVIOUS LIST, ITEM #35. MANY
 CHANGES WERE DONE TO THE PLAN AND NOT
 INDICATED IN ANY MANNER.
  
 9.)ADDITIONAL FEES DUE, $2163.60,
 BZ235307.PLEASE RETURN THE BZ GIVEN
 AT THE LAST REVIEW.
  
 10.)SEE PREVIOUS LIST, ITEM #12.NOT
 ADDRESSED.TO MY KNOWLEDGE THE PRODUCT
 APPROVALS SUBMITTED FOR DOORS AND
 WINDOWS DO NOT HAVE ANY FIRE RATING.
  
 11.)SEE PREVIOUS LIST, ITEM #13,
 INDICATE CONSTRUCTION TYPE ON THE PLAN.
  
 12.)SHEET 4, LSAT 2", MUST SPECIFY A
 MODEL #, NOT A DIMENSION.LSTA IS A
 WOOD-TO-WOOD CONNECTOR WHICH YOU ARE
 USING IN A WOOD-TO-MASONRY APPLICATION.
 EITHER SUBMIT DOCUMENTATION FROM THE
 MANUFACTURER SHOWING THAT THIS
 APPLICATION IS ACCEPTABLE, SPECIFY A
 DIFFERENT CONNECTOR, OR SUBMIT SEALED
 CALCULATIONS FOR THIS CONNECTOR IN THIS
 APPLICATION.CHECK ALL CONNECTORS.
  
 13.)THE WINDOW/DOOR BUCK DETAIL
 SPECIFIES "CASE HARDENEND NAILS",SPECIFY
 SIZE.THE FASTENERS FOR THE WINDOW
 CONFLICT WITH THE PRODUCT APPROVAL IN
 BOTH DIAMETER AND SPACING, SEE ATTACHED
 HIGHLIGHTED PRODUCT APPROVAL.
  
 14.)NOTE THAT THE TEMPERED WINDOWS
 SHOWN ON THE 2ND FLOOR ARE ALSO REQUIRED
 TO HAVE A FIRE RESISTANCE RATING, FBC
 1006.2.4.DOCUMENTATION SUBMITTED FOR
 THIS WINDOW IS TO SHOW COMPLIANCE WITH
 CHAPTER 16, FBC2405.2, AND FBC1006.2.4.
  
 15.)THE GUARDRAIL IS TO BE A MINIMUM
 OF 44", FBC1015.2.THE DETAILS SHOW
 THE STAIRRAIL (WHICH SERVES AS A
 GUARDRAIL) AT 30" AND 36".
  
 16.)HANDRAIL REQUIRED FOR STAIR ON
 BOTH SIDES, FBC1007.5.
  
 17.)SEE PREVIOUS LIST, ITEM #22,
 NOT ADDRESSED.
  
 18.)SEE PREVIOUS LIST, ITEM #24.
 ENERGY CALCS REQUIRED.
  
 19.)SEE PREVIOUS LIST, ITEM #25.
 RATHER THAN ADDRESS THE COMMENT THE
 INSULATION WAS REMOVED.INSULATION IS
 REQUIRED FOR THE FLOOR (OCCUPANCY
 SEPARATION) AND ROOF.
  
 20.)SEE PREVIOUS LIST, ITEM #29.NOT
 ADDRESSED.IF THE REQUIRED INFORMATION
 IS NOT SUBMITTED PRIOR TO PERMIT
 ISSUANCE, A SEPARATE PERMIT FOR SHUTTERS
 WILL BE REQUIRED.
  
 21.)SEE PREVIOUS LIST, ITEM #26.ALSO
 HAVE THE NEW PLANS APPROVED BY HISTORIC
 PRIOR TO RESUBMITTAL.
  
 22.)SPECIFY THE SPACING AND LENGTH OF
 THE ANCHOR BOLT, SHEET 4, WALL SECTION
 AT BALCONY.
  
 23.)SEPARATE PERMITS REQUIRED.
  
 24.)SEE PREVIOUS LIST, ITEM #37.NOT
 ADDRESSED.
  
 25.)RESOLVE ANY EXPIRED PERMIT ISSUES
 PRIOR TO ISSUANCE OF THIS PERMIT.
  
 26.)AS DISCUSSED SEVERAL TIMES WITH
 THE CONTRACTOR, IF YOU WISH TO OBTAIN A
 PERMIT FOR THE ROOF JOISTS, SHEATHING,
 AND ROOF COVERING ONLY, SUBMIT A PERMIT
 APPLICATION WITH PLANS SHOWING ONLY
 THESE ITEMS.PLANS ARE REQUIRED SHOWING
 DRAINAGE, DESIGN LOAD AND UPLIFT.
  
 27.)SLIDING GLASS DOOR PRODUCT
 APPROVALS WERE SUBMITTED, NONE SHOWN ON
 THE PLAN.
  
 28.)MULLION PRODUCT APPROVALS
 REQUIRED, SUBMIT 2 COPIES.
  
 29.)SHEET 2 IS NOW MISSING FROM THE
 OLD SETS OF PLANS.ALWAYS SUBMIT ALL
 OLD SHEETS WITH RESUBMITTAL.THE NEW
 SHEET 2 NOW SHOWS WINDOWS AS EXISTING.
 MY UNDERSTANDING IS THAT THIS BUILDING
 DOES NOT HAVE WINDOWS AND THAT THIS WORK
 IS TO BE INCLUDED IN THIS PERMIT.
 REVISE.
  
 30.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).
  
 31.)PAY FEES PRIOR TO RESUBMITTAL.
  
 32.)TWO COPIES OF ALL DOCUMENTATION
 REQUIRED FOR PERMITTING, ONLY ONE SET
 OF PLANS WERE SUBMITTED.
  
 33.)SEE PREVIOUS LIST, ITEM #6.THE
 FIRST FLOOR SHOULD BE DECLARED AS
 MERCANTILE, 2ND FLOOR AS R2 FBC CH.3.
  
 34.)SEE PREVIOUS LIST, ITEM #37.IN
 ADDITION TO PROVIDING THE REQUESTED
 INFORMATION FOR THE OCCUPANCY SEPARATION
 ALSO PROVIDE SAME FOR TENANT SEPARATION
 ON THE 1ST FLOOR, FBC704.3.1.
  
 35.)"EXISTING PLUMBING PIPE" IS SHOWN
 ON THE PLAN (SHEET2, 2ND FLOOR).
 PENETRATIONS ARE TO COMPLY WITH FBC705.2
 .1.3, 705.4.