Plan Review Notes For Permit 03111034 |
Permit Number |
03111034 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FLA. ADMIN. CODE | | FLA. STATUTES | | | | 1) SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS PER SECTIONS 1106, | | AND 1107 AND ALL SUBSECTIONS. SHOW LOC- | | ATION OF ALL PRIMARY ROOF DRAINS AND | | THE LOCATION OF SECONDARY OR OVERFLOW | | SCUPPER DRAINS. SUBMIT A DETAIL OF | | SCUPPERS. IF GUTTER AND DOWNSPOUTS, SHOW | | THE SIZE OF THE GUTTERS PER TABLE 1106.6 | | AND INDICATE SIZE OF DOWNSPOUTS. DOWN- | | SPOUTS SHALL TERMINATE MIN. OF 1' OFF | | SIDE OF STRUCTURE WALL. | | 2) THE PERSONAL SEAL, SIGNATURE AND DATE | | OF THE ARCHITECT SHALL APPEAR ON ALL | | DOCUMENTS TO BE FILED FOR PUBLIC RECORD, | | ***THE DATE IS MISSING.*** 61G1-16.003 | | FS 481.2055 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|