Plan Review Notes
Plan Review Notes For Permit 03111034
Permit Number 03111034
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106,
 AND 1107 AND ALL SUBSECTIONS. SHOW LOC-
 ATION OF ALL PRIMARY ROOF DRAINS AND
 THE LOCATION OF SECONDARY OR OVERFLOW
 SCUPPER DRAINS. SUBMIT A DETAIL OF
 SCUPPERS. IF GUTTER AND DOWNSPOUTS, SHOW
 THE SIZE OF THE GUTTERS PER TABLE 1106.6
 AND INDICATE SIZE OF DOWNSPOUTS. DOWN-
 SPOUTS SHALL TERMINATE MIN. OF 1' OFF
 SIDE OF STRUCTURE WALL.
 2) THE PERSONAL SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD,
 ***THE DATE IS MISSING.*** 61G1-16.003
 FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]