Plan Review Notes For Permit 03111034
Permit Number 03111034
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-05 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE A COPY OF A SURVEY FOR THIS
 PROPERTY.WHEN RESUBMITTING, ADDRESS
 FBC TABLE 600 ISSUES, IF ANY.
  
 2.)GIVE INFORMATION AS TO OCCUPANCY
 AND USE FOR THIS BUILDING.
  
 3.)SEE LETTER FROM HISTORICAL
 PRESERVATION DEPARTMENT DATED 11/20/03.
 BEFORE RESUBMITTAL HAVE THE EXTERIOR
 DOORS APPROVED.
  
 4.)THE APPLICATION INDICATES THAT YOU
 ARE REPLACING ALL WINDOWS AND DOORS.
 SHOW THE WINDOWS AND DOORS ON THE
 ELEVATIONS.ONE SET OF PLANS HAS
 WINDOWS PENCILLED IN.ALL EXISTING
 CONDITIONS SHOULD BE SHOWN.
  
 5.)REPAIRS AND ALTERATIONS OF OVER
 50% OF THE VALUE OF THE EXISTING
 BUILDING ARE REQUIRED TO COMPLY WITH
 FBC3401.7.2.6.
  
 6.)THE PLANS STATE "REHAB OF OFFICE
 BUILDING".THE CURRENT ZONING USE OF
 THIS BUILDING IS STORES ON 1ST FLOOR,
 APARTMENTS ON THE 2ND (SEE ATTACHED).
 PROVIDE INTENDED OCCUPANCY INFORMATION
 ON THE PLAN.
  
 7.)THE PERMIT APPLICATION IS FOR
 WINDOW REPLACEMENT.SLEEPING ROOMS ARE
 REQUIRED TO COMPLY WITH FBC1005.4,
 EMERGENCY EGRESS.INDICATE ANY FUTURE
 BEDROOMS ON THE PLAN AND SHOW COMPLIANCE
 BY SHOWING WINDOW SIZE, TYPE AND SILL
 HEIGHT.PROVIDE A WINDOW SCHEDULE.
  
 8.)SHOW TREAD AND RISER DIMENSIONS
 FOR THE EXTERIOR STAIR (FBC1007.3).
  
 9.)THE EXISTING STAIR RAILING DOES
 NOT COMPLY WITH FBC1007.5, FBC1015
 (HEIGHT, OPENINGS).PROVIDE A DETAIL
 FOR A NEW STAIR RAILING, ALSO SHOWING
 COMPLIANCE WITH FBC1608.2.
  
 10.) THE EXISTING GUARD RAILINGS
 (STAIR LANDING, BALCONIES) DO NOT COMPLY
 WITH FBC1015. PROVIDE A DETAIL FOR NEW
 GUARDRAILS, ALSO SHOWING COMPLIANCE WITH
 FBC1608.
  
 11.) STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE, FBC1007.5.2.
  
 12.) EXTERIOR STAIRS TO COMPLY WITH
 FBC1006.2.4.INDICATE, TO SCALE, ALL
 WINDOWS NEAR THE STAIR, WITH DIMENSIONS
 FROM THE STAIR.DOOR IS REQUIRED TO
 HAVE FIRE RATING AND DOOR CLOSER,
 SHOW ON PLAN AND PROVIDE FIRE RATING
 INFORMATION FOR DOOR, FBC1006.2.4.
  
 13.)INDICATE THE CONSTRUCTION TYPE
 ON THE PLAN.
  
 14.)PROVIDE A CONTRACT FOR THIS JOB;
 VALUE APPEARS LOW.IF A REASONABLE
 VALUE IS NOT PROVIDED FOR THIS JOB, AN
 ESTIMATE WILL BE DONE USING MARSHALL &
 SWIFT.THE AMOUNT ON THE APPLICATION IS
 FOR VALUE.A PERMIT WAS APPLIED FOR
 WITH THE SAME SCOPE OF WORK WITH A
 VALUE OF $35,000.
  
 15.)PROVIDE LOADING INFORMATION FOR
 THE FLOOR JOISTS, FBC1604.
  
 16.)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 17.) PROVIDE UPLIFT INFORMATION ON THE
 FLOOR AND ROOF PLAN.
  
 18.) PROVIDE A WINDOW AND DOOR BUCK
 DETAIL.
  
 19.) IN ORDER TO ISSUE A WINDOW PERMIT,
 SHOW ON THE PLAN ANY WINDOWS WHICH
 WOULD BE REQUIRED TO BE SAFETY GLASS
 PER FBC2405.2.
  
 20.) 1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 21.) 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 22.)INCLUDE WIND DESIGN INFORMATION
 REQUIRED TO BE ON THE PLAN, FBC1606.1.7,
 INCLUDING DESIGN PRESSURES FOR WINDOWS
 AND DOORS.
  
 23.)PROVIDE A SPECIFICATION FOR THE
 CONCRETE RESTORATION.IS WORK BEING
 DONE ON THE BALCONIES?
  
 24.)FBC 13-101.1.6SHELL BUILDINGS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED TO THE
 ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR
 INSTALLATION BY THE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 25.) INSULATION IS SHOWN IN THE FLOOR
 JOISTS, WHAT IS THE RVALUE?
  
 26.) AS PER THE LETTER FROM SHERRY
 PILAND DATED 11/20/03, GET HISTORIC
 APPROVAL FOR THE DOORS.
  
 27.) SUBMIT A SITE SPECIFIC PRODUCT
 APPROVAL OR STATEWIDE PRODUCT APPROVAL
 FOR THE FOLLOWING BEFORE INSTALLATION:
 HARTMAN OUTSWING WOOD FRENCH DOOR
 STANLEY OUTSWING DOOR
  
 28.) THE FOLLOWING PRODUCT APPROVALS ARE
 ON THE PENDING LIST.THIS PERMIT WILL
 BE ISSUED WITH A PROVISO THAT STATEWIDE
 OR SITE SPECIFIC PRODUCT APPROVAL BE
 SUBMITTED BEFORE INSTALLATION:
 JOHNS MANVILLE BUILT UP ROOF, FL1037
 BINNINGS PAN AMERICAN SINGLE HUNG
  
 29.) PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 30.) PRODUCT APPROVALS WERE SUBMITTED
 FOR ASPHALT SHINGLES, NONE ON THE PLAN.
 ALSO PLEASE NOTE THAT FOUR DIFFERENT
 DOOR PRODUCT APPROVALS WERE SUBMITTED.
  
 31.) THE EXTRA PRODUCT APPROVALS BOUND
 AND MARKED "RETURN TO CONTRACTOR" DO NOT
 NEED TO BE RESUBMITTED.
  
 32.) ADDITIONAL FEES, SEE ATTACHED BZ
 233269.
  
 33.) SEPARATE PERMITS REQUIRED.
  
 34.) THERE IS AN OPEN PLAN REVIEW ON
 THIS ADDRESS FOR THE SAME SCOPE OF
 WORK, #03030708.THIS APPLICATION
 SHOULD BE VOIDED.
  
 35.) WHEN RESUBMITTING, CLEARLY MARK
 ALL CHANGES TO THE PLAN WITH CLOUDS OR
 TRIANGLES.SUBMIT BOTH THE OLD SHEETS
 AND NEW REVISED PLANS.SUBMIT A
 TRANSMITTAL LETTER EXPLAINING HOW EACH
 ITEM WAS ADDRESSED.
  
 36.) SEE ATTACHED, CONTRACTOR HAS 3
 EXPIRED OPEN ROOF PERMITS.ADDRESS OR
 FURTHER ACTION AGAINST YOUR LICENSE
 AND ABILITY TO OBTAIN PERMITS WILL BE
 TAKEN.
  
 37.) PROVIDE FIRE RATING INFORMATION
 ON THE PLAN (UL ASSEMBLY NUMBER) OR
 CALCULATED FIRE RESISTANCE (FBC709) FOR
 THE OCCUPANCY SEPARATION (BETWEEN THE
 FIRST FLOOR M, AND 2ND FLOOR, R),
 FBC 704.