Plan Review Notes
Plan Review Notes For Permit 03110954
Permit Number 03110954
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) SIGNATURE REQUIRED ON SEAL OF ENGIN-
 ER PER 61G15-23.002(1) & 471.025.
 INITALS NOT ACCEPTABLE PER FBPE AND BLDG
 OFFICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]