2003-12-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE STATED PROJECT VALUE WAS UNDER-
 ESTIMATED.CITY OF WEST PALM BEACH
 ESTIMATES THE VALUE AT $35,100.THIS,
 IN ADDITION TO RADON AND FIRE REVIEW
 FEES DUE AND ALLOWING FOR THE $202.00
 ALREADY PAID, LEAVES AN OUTSTANDING
 PERMIT APPLICATION BALANCE OF $584.72 TO
 BE PAID.
  
 3) SHEET SP1.01, SITE PLAN.TWO CABANA/
 CLUBHOUSE BUILDINGS ARE SHOWN IN
 DIFFERENT LOACATIONS, SECTION-1 AND
 SECTION-2.ALSO, THE PERMIT APPLICATION
 FORM STATES SECTION 3-B.AMEND/ANNOTATE
 THE SITE PLAN AND PERMIT APPLICATION
 FORM TO CLARIFY THE LOCATION OF THE
 CABANA/CLUBHOUSE RELEVANT TO THIS PERMIT
 APPLICATION.
  
 4) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)
  
 5) FBC 1012.1.2THE ENTRANCE GATE SHALL
 OPEN IN THE DIRECTION OF EGRESS.
  
 6) SHEET S-4.TWO USP DTC EMBEDDED
 TRUSS ANCHORS ARE SPECIFIED AT EACH END
 OF THE HIP GIRDER TRUSS FOR THE MAIN
 (CENTRAL) ROOF.THE 2003 USP CATALOGUE
 STIPULATES THAT DTC "INSTALLATIONS
 SHOULD BE SPACED NO CLOSER TOGETHER THAN
 8" CENTER-TO-CENTER", THERE IS NO
 'DOUBLE ANCHOR APPLICATION' CHART.
 AMEND THE PLAN TO SPECIFY AN APPROPRIATE
 ANCHOR.
  
 7) SUBMIT A PRODUCT APPROVAL FOR THE
 ROOF TILE. THE SUBMITTED M-D PRODUCT
 APPROVAL NOA# 01-0705.02 FOR THE STEEL
 DOOR AND FENESTRATION TESTING LABORATORY
 REPORT FOR THE ALUMINUM FIXED WINDOW ARE
 NO LONGER SUFFICIENT FOR PRODUCT
 APPROVAL PURPOSES IN FLORIDA (SEE NOTE
 BELOW). SUBMIT SUPPORTING INFORMATION OR
 ALTERNATIVE PRODUCT APPROVAL DOCUMENTS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 8) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS