2004-01-26 00:00:00 | DENIED: 2ND REQUEST | | 1.RETURN AIR FROM THE MASTER BEDROOM | | IS NOT SIZED PROPERLY.PER 2001 FBC(M) | | EXCEPTION #1 & 3, ALL SUPPLY AIR TO THE | | MASTER SUITE SHALL BE INCLUDED IN THE | | CALCULATION FOR TOTAL SUPPLY AIR.THE | | RETURN SHALL BE A MINIMUM OF 1 1/2 TIMES | | THE SQUARE INCHES OF THE SUPPLY AIR TO | | THAT AREA. | | | | 2.PLEASE CLARIFY DUCT SIZE TO THE | | MASTER SUITE, 20" X 10"?IF THIS IS | | CORRECT THE MINIMUM SIZE FOR THE RETURN | | AIR JUMPER SHALL BE 20". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|