Plan Review Notes
Plan Review Notes For Permit 03110816
Permit Number 03110816
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-24 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE THE PLANS TO INDICATE THE
 FOLLOWING FOR CODE COMPLIANCE.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER
 OFRECORD. PER FS/FAC 481.221 & 471.025
  
 2} PLEASE SEE THAT THE RISER INDICATES
 3-6/0 CONDUCTORS FEEDING PANEL"B".SHOW
 ACTUAL SIZE.SEE SCHEDULE.
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E.
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210.52.
 SEE REVIEWED PLANS.
  
 6} NOTE # 13 IN ELECTRICAL NOTES
 INCORRECTLY REFERS TO SLEEPING ROOM
 RECEPTACLES BEING ARC FAULT,PLEASE SEE
 210.12 REFERS TO ALL BRANCH CIRCUITS.
  
 7} PLEASE NOTE THAT THE 200 AMP EXISTING
 PANEL IS MARKED AS MLO AND SHOWN AS MCB
 ON THE RISER,PLEASE CORRELATE.
  
 8} PLEASE SHOW THE LOCATION OF THE NEW
 A/C EQUIPMENT ON THE PLAN,AND THE
 LOCATION OF THE DISCONNECTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718