| PLEASE REVISE THE PLANS TO INDICATE THE |
| FOLLOWING FOR CODE COMPLIANCE. |
| |
| 1} PLEASE NOTE THAT ALL PLANS |
| DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| ING A TITLE BLOCK, MUST BE SIGNED, |
| DATED AND SEALED BY THE ARCH/ENGINEER |
| OFRECORD. PER FS/FAC 481.221 & 471.025 |
| |
| 2} PLEASE SEE THAT THE RISER INDICATES |
| 3-6/0 CONDUCTORS FEEDING PANEL"B".SHOW |
| ACTUAL SIZE.SEE SCHEDULE. |
| |
| 3} PLEASE NOTE FRONT AND REAR |
| RECEPTS REQ`D PER 210.52E. |
| |
| 4} PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG. |
| |
| 5} PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2',6',12' RULE PER 210.52. |
| SEE REVIEWED PLANS. |
| |
| 6} NOTE # 13 IN ELECTRICAL NOTES |
| INCORRECTLY REFERS TO SLEEPING ROOM |
| RECEPTACLES BEING ARC FAULT,PLEASE SEE |
| 210.12 REFERS TO ALL BRANCH CIRCUITS. |
| |
| 7} PLEASE NOTE THAT THE 200 AMP EXISTING |
| PANEL IS MARKED AS MLO AND SHOWN AS MCB |
| ON THE RISER,PLEASE CORRELATE. |
| |
| 8} PLEASE SHOW THE LOCATION OF THE NEW |
| A/C EQUIPMENT ON THE PLAN,AND THE |
| LOCATION OF THE DISCONNECTS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |