Plan Review Notes For Permit 03110777 |
Permit Number |
03110777 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-11-21 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE SUBMIT A LOAD CALCULATION | | SHOWING EXISTING AND ALL NEW LOADS | | BEING ADDED(IG: A/C SYSTEM),ALSO | | INDICATE SIZE IN AMPERAGE,OF THE | | SERVICE, PER 215.5. | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR | | THIS WORK.PLEASE HAVE THE ELECTRICAL | | CONTRACTOR SUBMIT PLANS SHOWING THE | | SCOPE OF HIS WORK WITH THE APPLICATION | | PER 104.2.1 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718. |
|