Date Text
2004-04-10 00:00:00DENIED:
 1.PLAN SHEET M1.1 OUTSIDE AIR CALC FOR
 AHU 4 INDICATES 1 CFM PER SQ FT.PER
 2001 FBC (M) 403.4.1 MINIMUM VENTILATION
 SHALL BE 5 CFM PER PERSON OR 1.5 CFM PER
 SQ FT.
  
 2.PLAN SHEET M2.1 KEY NOTE #7
 INDICATES CO SENSOR SHALL BE SET AT 40
 PPM.PER 2001 FBC(M) 403.4 CO SENORS
 SHALL BE SET AT 25 PPM.PLEASE CLARIFY.
  
 SEE ALSO COMMENTS FROM ASST FIRE
 MARSHALL, MIKE CARSILLO.
  