Plan Review Notes For Permit 03110633 |
Permit Number |
03110633 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-04-10 00:00:00 | DENIED: | | 1.PLAN SHEET M1.1 OUTSIDE AIR CALC FOR | | AHU 4 INDICATES 1 CFM PER SQ FT.PER | | 2001 FBC (M) 403.4.1 MINIMUM VENTILATION | | SHALL BE 5 CFM PER PERSON OR 1.5 CFM PER | | SQ FT. | | | | 2.PLAN SHEET M2.1 KEY NOTE #7 | | INDICATES CO SENSOR SHALL BE SET AT 40 | | PPM.PER 2001 FBC(M) 403.4 CO SENORS | | SHALL BE SET AT 25 PPM.PLEASE CLARIFY. | | | | SEE ALSO COMMENTS FROM ASST FIRE | | MARSHALL, MIKE CARSILLO. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|