2004-04-09 00:00:00 | 1) ELECTRONIC SWITCHES, CHANIN AND |
| LOCK REQUIRED ON BACKFLOW DEVICE. |
| NO CHANGE NOTED TO PAGE C-4.2. |
| |
| 2) DOOR 147A IS NOT RATED PER THE DOOR |
| SCHEDULE. DOOR IS LOCATED IN RATED |
| WALL THEREFORE AN OPENING PROTECTIVE |
| IS REQUIRED. PLEASE REVISE PLANS |
| AS NECESSARY. |
| |
| 3) PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR HANDRAILS AND GUARDRAILS SHALL |
| MEET THE FLORIDA BUILDING CODE AND |
| THE FLORIDA FIRE PREVENTION CODE. |
| |
| 4) THE ABOVE GROUND FUEL STORAGE TANK |
| SHALL BE PROTECTED BY BOLLARDS TO |
| PREVENT MECHANICAL DAMAGE, BE LABELED |
| AS TO ITS DEISEL CONTENT, AND BE |
| PLACARDED IN ACCORDANCE WITH NFPA |
| 704. ALSO NO SMOKING SIGNS SHALL |
| BE PROVIDED. |
| |
| 5) THE FIRE DEPARTMENT CONNECTION FOR |
| THE FIRE SPRINKLER SYSTEM SHALL BE |
| PROVIDED WITH CLEAR ACCESS AND BE |
| PROVIDED WITH SEVEN FEET, SIX INCHES |
| OF CLEARANCE. |
| |
| 6) WHAT PREVENTS THE GENERATOR EXHAUST |
| FROM BACKFEEDING INTO THE AIR EXHAUST |
| LOUVERS. |
| |
| 7) ALL SMOKE DETECTORS SHALL BE MOUNTED |
| A MINIMUM OF THREE FEET FROM AIR |
| CONDITIONER DIFFUSERS. |
| |
| 8) PLEASE CLEARLY IDENTIFY ALL |
| EMERGENCY LIGHT FIXTURES ON THE PLAN. |
| |
| 9) THE OPENING FROM 50TH STREET SHOULD |
| BE WIDER BECAUSE SERVICE VEHICLES WILL |
| HAVE TO ENTER THOUGH THE SEPARATED |
| OPENING. THESE INCLUDE SANITATION |
| TRUCKS AND FUEL TRUCKS. THE DIVIDER |
| SERVES NO REAL PURPOSE BUT WOULD |
| PROVIDE A POTENTIAL FOR MISHAPS. |
| |