Plan Review Notes
Plan Review Notes For Permit 03110633
Permit Number 03110633
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-21 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002
 PLEASE INCLUDE PRINTED NAME AND LICENSE
 # OF ENGINEER ON TITLE BLOCK.
  
 2)NOTE: PLEASE SEE SOME ITEMS ARE
 WHITED OUT ON PLANS. WHITE OUT IS NOT
 PERMITTED ON SIGNED AND SEALED PLANS.
 FS 471/481
  
 3)NOTE: PLEASE SUBMIT SPECIFICATIONS
 FOR GENERATOR/ATS/ ETC.
 PLEASE INDICATE IF MCB IS LOCATED ON
 THE OUTSIDE OF GENERATOR W/ OUT EXSPOS-
 -URE OF LIVE PARTS IN VIOLATION OF
 NEC 110.27
  
 4)NOTE: PLEASE SHOW/INDICATE POINTS
 OF CONNECTION FOR GROUNDING OF TRANS-
 -FORMERS PER 250.30
  
 5)NOTE: PLEASE SEE RISER, CONDUCTORS
 FEEDING LPD ARE SHOWN AS 1/0'S TO A
 225A PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]