Date |
Text |
2003-12-08 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 FUEL GAS |
| FLA. ADMIN. CODE |
| FLA STATUTES |
| |
| 1) SHTS C-2.1 & C-4.1 WATER SERVICE IN- |
| DICATES A PRESSURE VAC BREAKER ON THE |
| WATER SERVICE. AN RPZ BACKFLOW IS REQ- |
| UIRED. 608.13.2 |
| 2) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| COMPLIANCE, INDUSTRIAL PRETREATMENT FOR |
| SIZING OF OIL/WATER INTECEPTOR. WASTE |
| ORD. #2938-96. (561) 837-4074 |
| 3) SHT L1 MORE INFORMATION REQUIRED ON |
| THE FOUNTAIN. WILL THERE BE DRAINAGE OR |
| WATER SUPPLIED TO THE FOUNTAIN? |
| 4) SEPARATE PLANS/PERMIT REQUIRED FOR |
| IRRIGATION. |
| 5) SHT A2.4 EQUIPMENT & ACCESSORIES SHC- |
| EDULE. CLAIRFY #42 GAS LINE OUTLET, IS |
| THIS NATURAL GAS, OR A FUEL LINE FOR THE |
| TRUCKS? |
| 6) SHT A5.1 TOILET ROOMS #113 & 122 |
| SHOWER STALLS SHALL BE ACCESSIBLE. SHOW |
| BENCH REQUIRED IN STALLS. |
| 7) SHT A5.1 DRINKING FOUNTAIN SHALL BE |
| ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH 11-4.15 AND ALL SUB- |
| SECTIONS. ALSO SHOW COMPLIANCE WITH |
| 11-4.1.3(10)(A) PROVISI0NS FOR THOSE WHO |
| HAVE DIFFICULTY BENDING OR STOOPING. |
| 8) SHT P2.2 THE FOLLOWING INFORMATION |
| WILL BE REQUIRED FOR GAS PERMIT APPLIC- |
| ATION. (SEPARATE PERMIT REQUIRED) |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| I. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| J. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| 9) SHT P2.3 INDIRECT WASTE FOR ICE MAKER |
| SHALL BE A FLOOR SINK. FLOOR DRAINS ARE |
| NOT APPROVED FOR INDIRECT WASTE. 802.3 |
| 10) SHT P2.3 KITCHEN/DINING ROOM. IN- |
| DIRECT WASTE REQUIRED FOR ICE MAKER ON |
| THE COUNTER. SUBMIT A DETAIL. 802.1.1 |
| 11) PLANS SHALL BE SIGNED. SEALED, AND |
| DATED BY THE ENGINEER/ARCHITECT OF REC- |
| ORD. INCLUDE ALL LICENSE NUMBERS ON |
| TITLE BLOCK AND CERTIFICATE OF AUTHOR- |
| IZATION IF APPLICABLE. 61G15-23.002/FS |
| 471.025 - 61G1-16.003-.004/FS481.2055 |
| 12) OTHER COMMENTS MAY FOLLOW AS THIS |
| PLAN REVIEW SHOWS THAT PLANS ARE ONLY |
| 90% COMPLETE. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |