2003-12-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 FUEL GAS
 FLA. ADMIN. CODE
 FLA STATUTES
  
 1) SHTS C-2.1 & C-4.1 WATER SERVICE IN-
 DICATES A PRESSURE VAC BREAKER ON THE
 WATER SERVICE. AN RPZ BACKFLOW IS REQ-
 UIRED. 608.13.2
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, INDUSTRIAL PRETREATMENT FOR
 SIZING OF OIL/WATER INTECEPTOR. WASTE
 ORD. #2938-96. (561) 837-4074
 3) SHT L1 MORE INFORMATION REQUIRED ON
 THE FOUNTAIN. WILL THERE BE DRAINAGE OR
 WATER SUPPLIED TO THE FOUNTAIN?
 4) SEPARATE PLANS/PERMIT REQUIRED FOR
 IRRIGATION.
 5) SHT A2.4 EQUIPMENT & ACCESSORIES SHC-
 EDULE. CLAIRFY #42 GAS LINE OUTLET, IS
 THIS NATURAL GAS, OR A FUEL LINE FOR THE
 TRUCKS?
 6) SHT A5.1 TOILET ROOMS #113 & 122
 SHOWER STALLS SHALL BE ACCESSIBLE. SHOW
 BENCH REQUIRED IN STALLS.
 7) SHT A5.1 DRINKING FOUNTAIN SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL SUB-
 SECTIONS. ALSO SHOW COMPLIANCE WITH
 11-4.1.3(10)(A) PROVISI0NS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 8) SHT P2.2 THE FOLLOWING INFORMATION
 WILL BE REQUIRED FOR GAS PERMIT APPLIC-
 ATION. (SEPARATE PERMIT REQUIRED)
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 9) SHT P2.3 INDIRECT WASTE FOR ICE MAKER
 SHALL BE A FLOOR SINK. FLOOR DRAINS ARE
 NOT APPROVED FOR INDIRECT WASTE. 802.3
 10) SHT P2.3 KITCHEN/DINING ROOM. IN-
 DIRECT WASTE REQUIRED FOR ICE MAKER ON
 THE COUNTER. SUBMIT A DETAIL. 802.1.1
 11) PLANS SHALL BE SIGNED. SEALED, AND
 DATED BY THE ENGINEER/ARCHITECT OF REC-
 ORD. INCLUDE ALL LICENSE NUMBERS ON
 TITLE BLOCK AND CERTIFICATE OF AUTHOR-
 IZATION IF APPLICABLE. 61G15-23.002/FS
 471.025 - 61G1-16.003-.004/FS481.2055
 12) OTHER COMMENTS MAY FOLLOW AS THIS
 PLAN REVIEW SHOWS THAT PLANS ARE ONLY
 90% COMPLETE.
  