Plan Review Notes
Plan Review Notes For Permit 03110633
Permit Number 03110633
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-09 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
 1.OUTSIDE AIR CALCUALTIONS PER 2001
 FBC(M) 403.3, FOR ALL AREAS.
  
 2.AHU #3 NOT LOCATION NOT SHOWN ON
 THE PLAN (MECH RM 106?).
  
 3.CU-5 INDICATED ON PLAN SHEET M2.1
 AND IS NOT LISTED ON THE EQUIPMENT
 SCHEDULE ON SHEET M4.1.PLEASE CLARIFY.
  
 4.VENTILATION FANS 6 & 7.PLEASE
 CLARIFY WHEN THESE FANS ARE IN OPERATION
 (WHILE ROLL-UP DOORS ARE CLOSED/OPEN?).
 WILL THE APPARATUS BAY HAVE MECHANICAL
 EXHAUST WHEN THE DOORS ARE CLOSED?
  
 5.PLAN SHEET A2.3 INDICATES 2 KITCHEN
 SUPPLY FANS AND NO KITCHEN EXHAUST.
 PLEASE NOTE, 10 FT SEPARATION BETWEEN
 EXHAUST TERMINATION & FRESH AIR INTAKES
 OR HORIZONTALLY FROM PARTS FOR THE SAME
 OR CONTIGUOUS BUILDINGS (REFERENCE A7.2
 EXHAUST FAN DETAIL).
  
 6.ADDITIONAL PERMIT REQUIRED FOR HOOD
 AND FIRE SUPPRESSION.PLEASE PROVIDE
 THE FOLLOWING INFORMATION WITH PERMIT
 APPLICATION.
 A) PLANS INDICATING DUCT LAYOUT
 B) TERMINATION OF EXHAUST
 C) CLEARANCE TO COMBUSTIBLES PER NFPA
 96 1-3.2 & 2001 FBC(M)506.3.8.
 D) MANUFACTURER SUBMITTAL FOR THE HOOD
 E) EXHAUST FAN SHALL BE A HINGED
 UPBLAST. (DETAIL M3.3)
 F) SHOW COMPLIANCE WITH NFPA 96 &
 FBC(M) 506.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
  
 8.PLAN SHEET P2.1 INDICATES FUEL OIL
 DAY TANK.SHEET E4.1 INDICATES THE DAY
 TANK IS A SUBBASE TO THE GENERATOR -
 PLEASE CLARIFY.
  
 9.ADDITIONAL PERMIT REQUIRED FOR FUEL
 OIL.
  
 10. PROVIDE PIPING DETAIL FOR THE
 CONDENSATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.