2003-12-09 00:00:00 | DENIED: |
| PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW: |
| 1.OUTSIDE AIR CALCUALTIONS PER 2001 |
| FBC(M) 403.3, FOR ALL AREAS. |
| |
| 2.AHU #3 NOT LOCATION NOT SHOWN ON |
| THE PLAN (MECH RM 106?). |
| |
| 3.CU-5 INDICATED ON PLAN SHEET M2.1 |
| AND IS NOT LISTED ON THE EQUIPMENT |
| SCHEDULE ON SHEET M4.1.PLEASE CLARIFY. |
| |
| 4.VENTILATION FANS 6 & 7.PLEASE |
| CLARIFY WHEN THESE FANS ARE IN OPERATION |
| (WHILE ROLL-UP DOORS ARE CLOSED/OPEN?). |
| WILL THE APPARATUS BAY HAVE MECHANICAL |
| EXHAUST WHEN THE DOORS ARE CLOSED? |
| |
| 5.PLAN SHEET A2.3 INDICATES 2 KITCHEN |
| SUPPLY FANS AND NO KITCHEN EXHAUST. |
| PLEASE NOTE, 10 FT SEPARATION BETWEEN |
| EXHAUST TERMINATION & FRESH AIR INTAKES |
| OR HORIZONTALLY FROM PARTS FOR THE SAME |
| OR CONTIGUOUS BUILDINGS (REFERENCE A7.2 |
| EXHAUST FAN DETAIL). |
| |
| 6.ADDITIONAL PERMIT REQUIRED FOR HOOD |
| AND FIRE SUPPRESSION.PLEASE PROVIDE |
| THE FOLLOWING INFORMATION WITH PERMIT |
| APPLICATION. |
| A) PLANS INDICATING DUCT LAYOUT |
| B) TERMINATION OF EXHAUST |
| C) CLEARANCE TO COMBUSTIBLES PER NFPA |
| 96 1-3.2 & 2001 FBC(M)506.3.8. |
| D) MANUFACTURER SUBMITTAL FOR THE HOOD |
| E) EXHAUST FAN SHALL BE A HINGED |
| UPBLAST. (DETAIL M3.3) |
| F) SHOW COMPLIANCE WITH NFPA 96 & |
| FBC(M) 506. |
| |
| 7. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| |
| 8.PLAN SHEET P2.1 INDICATES FUEL OIL |
| DAY TANK.SHEET E4.1 INDICATES THE DAY |
| TANK IS A SUBBASE TO THE GENERATOR - |
| PLEASE CLARIFY. |
| |
| 9.ADDITIONAL PERMIT REQUIRED FOR FUEL |
| OIL. |
| |
| 10. PROVIDE PIPING DETAIL FOR THE |
| CONDENSATE. |
| |