Plan Review Notes
Plan Review Notes For Permit 03110633
Permit Number 03110633
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-11-26 00:00:001) SITE PLAN DOES NOT REFLECT
 EXISTING FIRE HYDRANT LOCATIONS.
  
 2) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON THE FIRE LINE BACKFLOW DEVICE.
  
 3) THE AUTOMATIC GATE ON 50TH STREET
 SHALL PROVIDE AT LEAST 20 FEET IN
 CLEAR WIDTH.
  
 4) PLEASE INDICATE ON PLANS WHICH
 OFFICE WILL BE FOR THE FIRE
 PREVENTION BUREAU.
  
 5) NO FIRE EXTINGUISHER SHOWN
 IN COMMUNITY/TRAINING ROOM.
  
 6) ROOM NEAR RADIO EQUIPMENT IS
 NOT LABELED.
  
 7) PROVIDE DETAILS ON FUEL TANK.
 PLEASE DISPLAY BARRIER PROTECTION,
 WARNING LABELS, AND PROVIDE PRODUCT
 APPROVALS.
  
 8) ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 9) ROOF PLAN DISPLAYS TWO KITCHEN
 SUPPLIES AND NO EXHAUST. PLEASE CORRECT.
 THE KITCHEN EXHAUST DUCT TERMINATION
 SHALL HAVE AT LEAST 10 FEET SEPARATION
 FROM KITCHEN SUPPLY.
  
 10) THE BUILDING ADDRESS IS REQUIRED
 ON THE CORRECT ELEVATION. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 11) THE FIRE HYDRANT AND THE FIRE
 DEPARTMENT CONNECTION SHALL BE
 PROVIDED WITH 7'-6" OF CLEARANCE.
  
 12) THE GENERATOR EXHAUST SHALL BE
 A MINIMUM OF AT LEAST 10 FEET FROM
 ANY BUILDING OPENINGS.
  
 13) THE LIGHTING PLAN DOES NOT MATCH
 THE LIFE SAFETY PLAN.
  
 14) THE FIRE ALARM SYSTEM IS TO BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910