2003-12-11 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) WHEN THE PLANS ARE SUBMITTED FOR |
| PERMIT, THE TITLE BLOCK ON EACH SHEET |
| SHALL INCLUDE THE SIGNATURE, SEAL AND |
| PRINTED LICENSE NUMBER OF ARCHITECT OR |
| ENGINEER OF RECORD. |
| |
| 2) THE PLANS ARE STATED AS BEING 90% |
| COMPLETE.THE FOLLOWING REVIEW COMMENTS |
| ARE BASED ON THE INCOMPLETE PLANS |
| SUBMITTED. |
| |
| 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE CODE COMPLIANCE FORMS |
| |
| 4) SUBMIT PRODUCT APPROVALS FOR THE |
| SPANISH 'S' TILE AND FOR THE BUILT UP |
| ROOFING. |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| |
| 5) SUBMIT PRODUCT APPROVALS FOR THE |
| WINDOWS, GLASS BLOCK, EXTERIOR DOORS AND |
| SIDELITES, HURRICANE SHUTTERS AND ROLL- |
| UP DOORS. |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| |
| 6) SHEET A6.1THE WINDOW SCHEDULE IS |
| INCOMPLETE. |
| |
| 7) SHEET A2.5THE WALL TYPES PLAN |
| LEGEND SHOULD BE AMENDED TO REFER TO |
| SHEET A2.6 FOR THE WALL TYPE DETAILS. |
| ALSO THE PLAN DOES NOT SHOW A WALL TYPE |
| FOR MANY OF THE WALLS (JUST SHOWN AS |
| TYPE X). |
| |
| 8) FBC 2405.2SHEET A2.5 SHOWS A NUMBER |
| OF INTERIOR WALLS WHICH APPEAR TO BE |
| GLAZED WITHIN 24 INCHES OF DOORS.THESE |
| ARE'HAZARDOUS LOCATIONS' AND ARE |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201).SUBMIT DETAILS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 9) FBC 11-4.24.4SHEET A5.3, SECTION 6A |
| THE PANTRY SINK SHALL BE MAXIMUM 6-1/2" |
| DEEP.ANNOTATE THE PLANS ACCORDINGLY. |
| |
| 10) SHEET A6.4, SECTION 1.WHERE DOES |
| THIS DETAIL OCCUR?SHOULD IT BE CALLED |
| UP ON SHEET A4.3, SECTION 2?ANNOTATE |
| THE PLANS TO SHOW THE LOCATIONS WHERE |
| THIS DETAIL OCCURS. |
| |
| 11) FBC TABLE 1606SHEET S-3, CODES |
| AND STANDARDS NOTE #1.FOR A FIRE |
| RESCUE STATION, THE IMPORTANCE FACTOR |
| SHOULD BE 1.15 (NOT 1.0).AMEND THE |
| NOTE AND MAKE ANY NECESSARY DESIGN |
| CHANGES. |
| |
| 12) SHEET S-3, WIND LOAD SCHEDULE.THE |
| ZONE 3 ROOF WIND SUCTION LOAD SHOULD BE |
| -78.3 PSF (NOT -38.3 PSF).AMEND THE |
| PLAN. |
| |
| 13) SHEET S-4, SECTION 6.THE MONOSLOPE |
| TRUSSES FOR THE LOWER ROOF ARE SHOWN |
| SUPPORTED BY LEDGERS BOLTED INTO THE |
| BOND BEAM.SHEET S-2 (ROOF PLAN) SHOWS |
| THE TRUSSES TIED DOWN WITH TYPE N |
| ANCHORS WHICH ARE SIMPSON HHETA 20. THAT |
| TYPE OF ANCHOR IS NOT SUITABLE FOR |
| CONNECTION BETWEEN WOOD LEDGERS AND A |
| WOOD TRUSS SUBJECT TO UPLIFT.AMEND THE |
| PLAN TO SPECIFY A SUITABLE ANCHOR. |
| |
| 14) INFORMATIVE: |
| SHEET S-3, TRUSS TIE DOWN SCHEDULE.IT |
| IS NOTED THAT ONLY ANCHOR TYPES B,D & N |
| ARE SPECIFIED ON THE ROOF PLAN.NOTE |
| THAT ANCHOR TYPES J & K ARE LISTED AS |
| 'HUGHES' ANCHORS, AND THAT COMPANY NO |
| LONGER SUPPLIES TRUSS ANCHORS. |
| |
| 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |