2005-02-15 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| BUTLER MANUFACTURING METAL BUILDING |
| SHOP DRAWINGS SUBMITTED ON 2/2/05 AND |
| RE-SUBMITTED ON 2/14/05. |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 1804.4FOOTING DESIGN.THE |
| FOUNDATION REACTION TABLE FOR THE FRAME |
| AT SIDEWALL GRIDS 2 & 4 (BUTLER DRAWING |
| NO. D05-124126-01A) GIVES A MAXIMUM |
| POSITIVE REACTION OF 46.2 KIPS FOR THE |
| COLUMNS AT GRIDS A AND E.STRUCTURAL |
| SHEET S-1 SPECIFIES A 4'-0" X 4'-0" PAD |
| FOOTING AT EACH OF THESE FOUR COLUMN |
| LOCATIONS.THE GROUND BEARING PRESSURE |
| WILL EXCEED THE SOIL BEARING CAPACITY OF |
| 2500 PSF, STATED ON SHEET A-1.AMEND |
| THE PLANS OR SUBMIT CALCULATIONS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 2) FBC 1804.4FOOTING DESIGN.SIMILAR |
| TO THE ABOVE COMMENT, THE FOUNDATION |
| REACTION TABLE FOR THE ENDWALL FRAME AT |
| SIDEWALL GRID 6 (BUTLER DRAWING NO. |
| D05-124126-01A) GIVES A MAXIMUM POSITIVE |
| REACTION OF 11.6 KIPS FOR THE COLUMN AT |
| GRID E.STRUCTURAL SHEET S-1 SPECIFIES |
| A 2'-0" X 2'-0" PAD FOOTING FOR THIS |
| COLUMN LOCATION.THE GROUND BEARING |
| PRESSURE WILL EXCEED THE SOIL BEARING |
| CAPACITY OF 2500 PSF, STATED ON SHEET |
| A-1.AMEND THE PLANS OR SUBMIT |
| CALCULATIONS TO DEMONSTRATE COMPLIANCE. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |