2005-02-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 BUTLER MANUFACTURING METAL BUILDING
 SHOP DRAWINGS SUBMITTED ON 2/2/05 AND
 RE-SUBMITTED ON 2/14/05.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1804.4FOOTING DESIGN.THE
 FOUNDATION REACTION TABLE FOR THE FRAME
 AT SIDEWALL GRIDS 2 & 4 (BUTLER DRAWING
 NO. D05-124126-01A) GIVES A MAXIMUM
 POSITIVE REACTION OF 46.2 KIPS FOR THE
 COLUMNS AT GRIDS A AND E.STRUCTURAL
 SHEET S-1 SPECIFIES A 4'-0" X 4'-0" PAD
 FOOTING AT EACH OF THESE FOUR COLUMN
 LOCATIONS.THE GROUND BEARING PRESSURE
 WILL EXCEED THE SOIL BEARING CAPACITY OF
 2500 PSF, STATED ON SHEET A-1.AMEND
 THE PLANS OR SUBMIT CALCULATIONS TO
 DEMONSTRATE COMPLIANCE.
  
 2) FBC 1804.4FOOTING DESIGN.SIMILAR
 TO THE ABOVE COMMENT, THE FOUNDATION
 REACTION TABLE FOR THE ENDWALL FRAME AT
 SIDEWALL GRID 6 (BUTLER DRAWING NO.
 D05-124126-01A) GIVES A MAXIMUM POSITIVE
 REACTION OF 11.6 KIPS FOR THE COLUMN AT
 GRID E.STRUCTURAL SHEET S-1 SPECIFIES
 A 2'-0" X 2'-0" PAD FOOTING FOR THIS
 COLUMN LOCATION.THE GROUND BEARING
 PRESSURE WILL EXCEED THE SOIL BEARING
 CAPACITY OF 2500 PSF, STATED ON SHEET
 A-1.AMEND THE PLANS OR SUBMIT
 CALCULATIONS TO DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO